Transformer Full Load Amps Calculator
Enter nameplate kVA, phase, and both winding voltages to calculate primary and secondary FLA together. Default: 100 kVA, 480 V → 208 V, three-phase.
Quick calculator
Use line-to-line voltage for three-phase. Results update instantly.
Advanced calculator
Scale winding currents by operating load. Nameplate FLA still shown at 100%.
100% = nameplate FLA. Use 70–90% for typical continuous plant loading.
About this calculator
See our power calculators on the hub. This is a transformer nameplate task: it reports both winding currents in one result. For a generic one-side conversion, use kVA to Amps; for equipment capacity, use Transformer Size. Browse the power calculator hub.
Primary and secondary FLA
Result explanation
Primary FLA: 120.3 A @ 480 V · Secondary FLA: 277.6 A @ 208 V.
Assumptions: Screening only. Verify the nameplate, tap position, conductor conditions, OCPD rules, and available fault current before procurement.
Continue Your Calculation
After you know both winding FLA values, screen transformer %Z and equipment SCCR before preliminary protection review.
Common three-phase transformer FLA chart
| kVA | 208 V | 480 V | 600 V |
|---|---|---|---|
| 75 | 208 A | 90 A | 72 A |
| 100 | 278 A | 120 A | 96 A |
| 150 | 416 A | 180 A | 144 A |
| 500 | 1,388 A | 601 A | 481 A |
Transformer full-load current formula
Three-phase: FLA = kVA × 1,000 ÷ (√3 × line-to-line V). Single-phase: FLA = kVA × 1,000 ÷ V. PF is not used because transformer nameplate capacity is already kVA.
Example: 100 kVA, 480 V, 3φ: 100,000 ÷ (1.732 × 480) = 120.3 A. At 208 V secondary: 277.6 A.
Workflow: load → transformer kVA → this FLA tool → %Z fault screen → breaker screening.
Use the right tool
Generic kVA to Amps handles any load side. This page is for a transformer with known primary and secondary voltages. Use SCCR Calculator when you also need to compare a marked SCCR / kAIC rating.
Frequently asked questions
How do I calculate transformer full-load amps?
Use kVA and the voltage of the winding you are checking. For three-phase, divide kVA × 1,000 by √3 × line-to-line voltage.
How many amps is a 100 kVA transformer?
At 480 V three-phase it is about 120.3 A; at 208 V three-phase it is about 277.6 A. Voltage side matters.
Is primary current the same as secondary current?
No. The lower-voltage winding carries more current for the same kVA.
Does FLA choose the breaker size?
No. It is an input to preliminary protection review; code and manufacturer rules still apply.
Related Tools
- Available Fault Current Calculator
- Breaker Size Calculator
- Transformer kVA Calculator (Instant Free Sizing & Chart)
- kVA to Amps Calculator (Instant, Free) — Also Amps to kVA
- Transformer Turns Ratio Calculator (Instant, Free, with Formula & Examples)
- Factory Load Calculator
- Electricity Load Factor Calculator
- Battery Runtime Calculator (Instant, Free) — Ah & Load → Hours
Related Guides
- Transformer Sizing Guide — Complete guide to transformer capacity calculation, kVA sizing, and load matching
- Transformer Rating Calculation — How to calculate transformer kVA rating from load current, voltage, and power factor
- Three-Phase Transformer Sizing — Step-by-step 3-phase transformer sizing with diversity factors and safety margins
- Transformer Efficiency & Loss Calculation — Calculate copper losses, core losses, and efficiency at different load levels