Breaker Size Calculator

What size breaker do you need? Screen the next standard frame from load amps or watts/kW with a duty margin (125% continuous / 150% motor). Example: 32 A @ 125% → 40 A. Use the calculator below—not coordination, AIC, or code-table replacement.

Calculator

Quick: design amps and duty class. Advanced: convert kW/watts at voltage and phase, then apply continuous vs motor margin before picking a frame.

Coming from power calculations?

First calculate your current:

kW → kVAkVA → Amps
Load input
Typical: small loads 10-30 A, feeders 100-300 A, main incomer 400 A+.
Quick examples
Use 125% for continuous loads, 150% as a starting point for motors, 100% for short-duty or non-continuous circuits.

About this calculator

Turns load current (or kW/watts via voltage and phase) and a safety factor into the next standard circuit breaker frame for planning before coordination and interrupting ratings. Use it as a free breaker sizing calculator for OCPD screening. For cable and feeder checks in the same workflow lane, use the protection calculators hub.

Calculation Results

Calculation Results

Load Current: 32.00 A
Safety Factor: 125% (continuous load) (× 1.25)
Calculated Current: 40.00 A
Recommended Breaker Size: 40 A (next standard size above 40.0 A)
Engineering disclaimer

This calculator provides simplified breaker sizing for preliminary engineering only. Final protection device selection must follow applicable standards (IEC/NEC), manufacturer data, short-circuit studies, and coordination checks by a qualified engineer.

Standard breaker frame — quick reference

Common IEC/NEC-style frames used in this calculator’s ladder (aligned with typical NEC 240.6(A) standard ampere ratings). Multiply design load by your duty margin, then pick the next standard rating at or above the product.

Load (A) Margin Product (A) Next frame (A)
12125% continuous1515
16125% continuous2020
24125% continuous3030
32125% continuous4040
48125% continuous6060
63125% continuous78.880
80125% continuous100100
90125% continuous112.5125
48150% motor (430.52 screen)7280
100150% motor (430.52 screen)150150

NEC 240.6(A) — common standard ampere ratings

Standard OCPD ampere ratings commonly used for screening (not a full code reprint). After load × margin, round up to the next value on this ladder.

15 · 20 · 25 · 30 · 35 · 40 · 45 · 50 · 60 · 70 · 80 · 90 · 100 · 110 · 125 · 150 · 175 · 200 · 225 · 250 · 300 · 350 · 400 · 450 · 500 · 600 A

Breaker size vs typical copper wire (screening)

Illustrative pairing only—confirm ampacity, temperature rating, and local code. For project mm² from design amps, use the Cable Size Calculator.

Breaker (A) Typical Cu (AWG) Typical Cu (mm²) Common use
1514 AWG2.5Lighting / general outlets
2012 AWG2.5–4Kitchen / small appliance
3010 AWG4–6Dryer / water heater screen
408 AWG6–10Range / 32 A EV continuous
506 AWG10Range / hot tub screen
606 AWG10–16Subfeed / larger EV
1003–1 AWG25–35Sub-panel feeder screen

How to Calculate Breaker Size (Formula & Explanation)

Circuit breaker sizing formula: Breaker Size (A) = Load Current (A) × Safety Factor → next standard frame on the 240.6(A) ladder.

This breaker sizing calculator path is the same workflow people search as a circuit breaker calculator: start from amps (or convert kW/watts), apply continuous/motor margin, then pick the next standard OCPD frame.

If you know power instead of amps: single-phase I = P ÷ (V × PF); three-phase I = P ÷ (√3 × V × PF) with P in watts (kW × 1000). Then apply the same duty margin and round up.

80% rule vs 125% continuous (NEC practice)

US panel practice often says a breaker should not carry more than 80% of its rating for continuous loads (3 hours or more). That is the same math as sizing the breaker at 125% of continuous current: continuous load ÷ 0.80 = load × 1.25.

  • Example: 32 A continuous → 32 × 1.25 = 40 A → select a 40 A frame (load is 80% of 40 A).
  • Noncontinuous loads may screen closer to 100% of frame ampacity—still match conductor ampacity and local amendments.
  • This calculator’s default 125% duty mirrors the continuous-load screen; use 150% only as a motor starting screen (below).

NEC 430.52 — motor branch-circuit short-circuit / ground-fault screen

NEC 430.52 sets maximum percentages of motor full-load current for inverse-time breakers and other devices protecting motor branch circuits. A common planning screen is about 250% of FLA as an upper bound for inverse-time breakers (exact table values depend on motor type and device)—this tool’s 150% factor is a conservative starting frame for inrush, not a substitute for Table 430.52 or manufacturer MOCP.

Example: Motor FLA 48 A × 150% = 72 A → next frame 80 A. Confirm overload (430.32), conductor size, and starting method with the Motor Starting & Protection guide.

NEC 450.3 — transformer primary / secondary OCPD

Transformer primary and secondary breaker limits follow NEC 450.3 (percentage of rated primary/secondary current by voltage and supervision), not the generic continuous 125% path alone. Size kVA and currents first with the Transformer Size Calculator, then apply 450.3 percentages to choose OCPD frames.

Final selection must also consider short-circuit rating, coordination with upstream devices, conductor ampacity, and local code requirements.

Last updated: 2026-07-29. Screening estimate only—verify against the adopted NEC edition, manufacturer data, and a qualified electrician/engineer.

References

Guides: Fuse vs Breaker Sizing · Motor Starting & Protection · Coordination & SCCR · Power Calculators Hub

Typical Examples & Frame Ladder

  • 32 A continuous panel load × 125% → 40 A frame (pair with ~8 AWG / 6–10 mm² Cu per chart).
  • Electric dryer ~24 A continuous × 125% → 30 A frame; confirm nameplate and 10 AWG (or local) conductors.
  • 32 A EV continuous × 125% → 40 A frame; do not upsize the breaker without matching wire and charger MCA/MOCP.
  • 90 A feeder × 125% → 125 A standard frame.
  • Motor branch with 150% factor → initial frame before NEC 430.52 / coordination study (see formula section).
  • Transformer primary/secondary OCPD → NEC 450.3 via the Transformer Size Calculator, not only 125% continuous.

Standard breaker frame ladder

Gray bars: common frames; blue bar: recommended frame; dashed line: load current; amber line: after safety margin.

Standard breaker frame ladder with recommended frame highlightedAmps → standard frame (A)15203040506080100125150160175200225250300400600Load× margin40 A frame

Screening only—not a trip curve, coordination study, or code table replacement.

Frequently Asked Questions

What size breaker do I need?

Find the load current (or convert watts/kW at your voltage and phase in the calculator), multiply by 1.25 for continuous loads (or 1.50 as a motor starting screen), then pick the next standard frame at or above that product. Example: 32 A × 125% → 40 A. Always match wire ampacity to the breaker—see the Cable Size Calculator for mm² screening.

What is a breaker size calculator?

A breaker size calculator (also called a circuit breaker calculator or breaker sizing calculator) estimates OCPD frame from load current × duty margin (125% continuous / 150% motor start), then picks the next standard rating. Example: 32 A × 125% → 40 A frame. Use after kVA to amps or factory load gives design amps—or enter kW directly above.

Is a circuit breaker calculator the same as breaker sizing?

Yes for preliminary amp rating. A circuit breaker calculator and a breaker sizing calculator both answer “what size breaker do I need?” from load current (or watts) and duty margin. Trip curves, AIC/SCCR, and selective coordination are separate steps after this screen.

What size breaker for a dryer, EV charger, or panel feeder?

Typical screens (always verify nameplate): electric dryer often ~24 A continuous → 30 A; 32 A EV continuous → 40 A; 90 A feeder × 125% → 125 A. Use the Quick examples buttons, then confirm conductors in the wire chart and cable sizing tool.

What is a breaker size calculator used for?

It is used to estimate a suitable breaker current rating from load current and safety factor during preliminary electrical design.

How do I calculate breaker size from load current?

First calculate the load current, then multiply by an appropriate safety factor (for example 125% for continuous load). Finally, select the next higher standard breaker size. This calculator automates those steps for you.

What is the standard breaker sizing formula?

The formula is Breaker Size (A) = Load Current (A) × Safety Factor, then round up to the next standard breaker rating.

Can you show a breaker size example?

Example: 80 A continuous load × 1.25 = 100 A, so select at least a 100 A standard breaker, then verify with coordination and code checks.

Can I replace a 20 amp breaker with a 30 amp breaker?

Usually no—not without checking the whole circuit. A 30 A breaker is only valid if the conductors, terminal ratings, and connected load are approved for 30 A continuous service under your code (NEC, IEC 60364, or local rules). Swapping a tripping 20 A breaker for a 30 A unit on the same wire often violates ampacity, reduces protection, and can create overheating. If the 20 A trips, diagnose overload, inrush, or a weak breaker first; if the load truly grew, upgrade wire size and equipment together, then pick the breaker from the calculator ladder.

What is the 80% rule for breakers?

For continuous loads (typically 3 hours or more), US panel practice keeps the load at about 80% of the breaker rating—the same as sizing the OCPD at 125% of continuous current. Example: 32 A × 1.25 → 40 A frame. See 80% rule vs 125% above.

Why do continuous loads often use 125%?

Continuous loads heat the breaker for long periods. A 125% factor helps prevent nuisance tripping and keeps the breaker operating within its thermal limits, following typical code practice for continuous current (inverse of the 80% rule).

How does NEC 430.52 affect motor breaker size?

NEC 430.52 caps motor branch-circuit short-circuit / ground-fault devices as a percentage of FLA (often up to ~250% for inverse-time breakers—check the table for your motor/device). This tool’s 150% option is a conservative starting frame for inrush, not a full 430.52 selection. See 430.52 screen and the motor protection guide.

When should I use 150% for motor loads?

Motors have inrush current that can be several times the running current. For many applications, using 150% as a starting point helps accommodate inrush while coordination and protection studies refine the exact rating under NEC 430.52 / manufacturer MOCP.

How do I size a breaker for a transformer?

Use NEC 450.3 percentages of primary/secondary rated current after you know transformer kVA and voltages—not only the generic continuous 125% path. Start with the Transformer Size Calculator, then apply 450.3. See 450.3 notes above.

What is motor FLA and how does starting current affect breaker sizing?

FLA (full-load amps) is the motor’s rated running current at nameplate HP/kW. LRA (locked-rotor amps) reflects starting inrush and can be 5–8× FLA. This calculator uses FLA × duty margin for frame screening—use 150% as a starting point, then refine with the motor starting & protection guide and SCCR checks in the SCCR calculator.

Does voltage affect breaker size?

Breaker current rating (A) is based on load current, but its voltage rating (for example 230 V, 400 V) must be suitable for the system. This tool focuses on current sizing; voltage and breaking capacity must be checked separately.

Is this calculator enough for final design?

No. It is a preliminary sizing tool. Final designs must include short-circuit calculations, coordination studies, cable sizing, ambient conditions, and must comply with IEC/NEC or local codes.

When should I use a fuse instead of a circuit breaker?

Use the same amp screening path here first. Fuses suit switchgear and MCC buckets where predictable I²t and spare links are acceptable; breakers suit panelboards where reset matters. See the Fuse vs Breaker Sizing Guide for decision tables and a 63 A feeder example.

How do selective coordination and SCCR fit after breaker sizing?

Amp screening here is step one only. Use the Protection Coordination & SCCR Guide with Short-Circuit Planning before final device selection.

What is the difference between MCB, MCCB, and fuse sizing?

MCB and MCCB are breaker frames; fuses are one-shot links. At screening stage, all use load current × margin → next standard amp rating. Trip curves, fuse class, and SCCR come later in coordination studies.