Cable Size Calculator: NEC 2023 AWG & mm² Screening
Use the cable size chart below or enter design amps / kW for an instant AWG + mm² screen (1φ/3φ, Cu/Al)—including solar / PV DC strings, 12 V battery, inverter, and VFD feeders—then verify derating, voltage drop, and protection. Not a conduit-fill calculator.
Calculator
Quick presets (PV DC / wire gauge / VFD)
Quick: design amps or kW + PF → line current → AWG screen + mm². Advanced: Ca/Cg derating + run length + 3%/5% VD upsize (ampacity and drop on one screen).
Inputs (amps or kW, voltage, phase, material)
Quick feeder screening for industrial and commercial panels—results show an NEC-style AWG screen plus the IEC mm² ladder. After you pick a candidate, validate long runs with the NEC voltage drop or IEC voltage drop calculator.
Line current is calculated and shown in the results; the amps field updates automatically.
Controls the AWG screening column only. Select 75°C only when permitted by the equipment listing/marking and adopted code.
Advanced — derating & run length
Enter correction factors from the adopted wiring code and the actual conductor insulation, ambient, installation and grouping conditions. The calculator does not choose these factors.
Tip: Switch to From kW for a one-step 3-phase cable size from load power, or keep amps for direct screening.
About this calculator
Turn design amps or kW + PF into an NEC-style AWG screen plus the next standard mm² from a fixed IEC ladder—optionally apply illustrative Ca/Cg derating—before you lock BOMs or panel schedules. For the same protection workflow lane, use the protection calculators hub; for long feeders after sizing, use the NEC / AWG voltage drop calculator. Deeper narrative: voltage drop calculation and Motor Starting Current & Protection.
Prefer From kW for a one-step 3-phase cable size (Ib = P ÷ (√3 × V × PF)), or keep From design amps when you already have line current from 3-phase power / kVA to amps.
Calculation Results
Calculation Results
System: Three Phase, 400 V, Copper conductor
Wire gauge screen (NEC 2023 Table 310.16, 60°C column): 4 AWG for ≈63 A Cu before installation corrections
Cable size screen (IEC mm² ladder): 16 mm²
Enter one-way run length under Advanced to prefill the NEC voltage drop or IEC voltage drop calculator.
IEC mm² ladder plus NEC 2023 Table 310.16 AWG screen for planning only. Optional Advanced Ca/Cg factors inflate screening current; this page does not apply small-conductor OCPD limits, parallel-conductor rules, terminal-temperature exceptions beyond the selected column, or short-circuit withstand.
Continue Your Calculation
Check the candidate conductor against the actual one-way route length. If voltage drop misses target, upsize the conductor and recheck breaker / OCPD coordination.
Engineering disclaimer
This calculator provides cable screening estimates only. For final electrical system design, conductor selection, and compliance with local electrical codes, consult a licensed electrical engineer or certified professional. Actual requirements may vary based on installation method, ambient conditions, harmonics, and specific application requirements.
Cable size chart (amps → AWG / mm²)
Field-style cable size chart / electric / battery cable sizing chart from the same IEC 60228-style ladder used in the calculator (typical copper screening). Click a current to load the calculator; verify tabulated ampacity after derating and voltage drop. AWG is an approximate NEC cross-check only—not conduit trade size.
| Design current (A) | Next standard Cu mm² (screening) | Approx. AWG (NEC ref.) |
|---|---|---|
| 1.5 | 16 AWG | |
| 2.5 | 14 AWG | |
| 4 | 12 AWG | |
| 6 | 10 AWG | |
| 10 | 8 AWG | |
| 16 | 6 AWG | |
| 25 | 4 AWG (IEC) / ~3 AWG @75°C NEC | |
| 35 | 2 AWG | |
| 50 | 1 AWG | |
| 70 | 2/0 AWG |
Conduit sizing for wire? This page sizes conductor ampacity, not raceway trade size. After you pick AWG/mm², use NEC Chapter 9 Annex C (or manufacturer fill tables) for conduit/EMT fill %. In conduit, still apply ambient + grouping derating (Advanced Ca/Cg) before locking the BOM.
Ambient & grouping derating — screening reference
Illustrative correction factors only—do not stamp these numbers into a final design. Enter Ca/Cg from the adopted edition tables (for U.S. projects typically NEC 2023 ambient/adjustment notes under Art. 310; elsewhere IEC 60364-5-52, BS 7671 Appendix 4, etc.). This calculator’s mm² ladder is underrated from design current; Advanced Ca/Cg only inflate the screening current.
Example ambient correction (illustration only — not a code reprint)
| Ambient (°C) | Correction factor |
|---|---|
| 21–25 | 1.00 |
| 31–35 | 0.94 |
| 41–45 | 0.88 |
| 51–55 | 0.82 |
Example bundling / grouping adjustment (NEC-style illustration)
| Current-carrying conductors in raceway/cable | Adjustment factor |
|---|---|
| 1–3 | 1.00 |
| 4–6 | 0.80 |
| 7–9 | 0.70 |
| 10–20 | 0.50 |
Combined derating example: Design current 63 A → screening ladder suggests 16 mm² Cu. If ambient 41–45 °C (factor 0.88) and 4–6 grouped conductors (factor 0.80), required tabulated ampacity ≥ 63 ÷ (0.88 × 0.80) ≈ 89 A → upsize to the next ladder step (often 25 mm² for Cu screening). Then check voltage drop and OCPD coordination.
OCPD type (fuse vs breaker): see Fuse vs Breaker Sizing Guide.
Cable sizing method & formula context
- I
- Design load current in amperes (RMS, steady-state basis you are sizing for).
- V
- Nominal system voltage in volts (line-to-neutral for single-phase, line-to-line for three-phase).
- mm²
- Conductor cross-sectional area per IEC 60228 standard sizes; output here is always an integer mm² step.
- Ampacity
- Tabulated allowable current for a conductor under stated conditions; must be derated for grouping, ambient, and installation method.
- PF (cos φ)
- Power factor when converting from kW to kVA before finding line current.
Obtain design current: single-phase I = kVA × 1000 ÷ V; balanced three-phase I = kVA × 1000 ÷ (√3 × V) with √3 ≈ 1.732. From kW: kVA = kW ÷ PF, then use the line-current formula for your phase.
Screening rule (this tool): pick the smallest standard mm² whose ladder step current is ≥ I (or ≥ It when Advanced Ca/Cg are set, with It = Ib ÷ (Ca × Cg)). This is not a substitute for manufacturer ampacity tables, harmonics, insulation temperature rating (for example XLPE 90 °C), or short-circuit/adiabatic withstand proofs.
Solar / PV DC strings (solar panel cable size calculator path): Click the PV DC string · 27.5 A preset (Isc 11 A × 2 parallel × 1.25 → often ~6 mm² / ~10 AWG before derating), or enter your own Isc × N_parallel × continuous-current factor from the series-parallel calculator. Method: how to size solar DC cable. Confirm with MPPT sizing and the Solar calculators hub—this page absorbs solar DC cable screening; not a separate PV-cable-only tool.
Worked example: Module Isc 11 A, 2 parallel → 11 × 2 × 1.25 = 27.5 A design. Enter 27.5 A (DC 2-wire) on this calculator—screening often lands near ~6 mm² / ~10 AWG before derating and voltage-drop upsizing. Then check one-way length under Advanced / voltage drop.
12 V / 24 V / 48 V battery & inverter DC: Enter continuous DC amps (or use Quick presets), set Phase to DC (2-wire) and voltage to 12/24/48. Ampacity screen gives AWG + mm²; then set one-way length (ft) under Advanced and open NEC voltage drop—low-voltage DC % loss climbs fast on long runs.
VFD / motor feeder screening: Use motor FLA × code factor (often 125%) as design amps, or the VFD preset (~63 A). This screens ampacity only—drive cable length, PWM reflections, and shield rules need manufacturer guidance after the ampacity + voltage-drop check.
Worked example (with numbers)
Given: 37 kW production load, PF 0.85, 400 V three-phase copper feeder.
Step 1 — kVA: 37 ÷ 0.85 ≈ 43.5 kVA.
Step 2 — line current: 43.5 × 1000 ÷ (1.732 × 400) ≈ 62.8 A → use 63 A design current.
Step 3 — screening mm²: 63 A maps to the next ladder step → 16 mm² Cu (integer output).
Step 4 — verify: apply grouping/ambient derating on project tables; check route length with the voltage drop calculator; confirm OCPD and fault current withstand with the breaker size calculator.
480 V three-phase · 100 A (SERP-style): Enter 100 A, 480 V, 3φ, Cu (or use the 480 V 3φ · 100 A preset). Screening often lands near 35 mm² / ~2 AWG before derating—then apply Ca/Cg and check NEC voltage drop for a 150 ft one-way run. This is a planning screen, not a full NEC Table 310.16 fill for every install method.
Common Cable Sizing Scenarios
Illustrative screening rows only—not a stamped bill of materials. AWG values below are read against NEC 2023 Table 310.16 copper columns under the stated temperature basis, ≤3 current-carrying conductors, and 30°C ambient before installation corrections. They do not auto-apply small-conductor OCPD limits (e.g. 240.4(D)-style), parallel-set rules, or terminal exceptions. Confirm on the locally adopted edition.
| Scenario | Load | Screening AWG (Cu) | mm² ladder | Screening notes |
|---|---|---|---|---|
| Electric water heater | 4500W @ 240V = 18.75A | 12 AWG | 4 mm² | If continuous, design often uses 125% → 23.4 A; verify OCPD/small-conductor rules |
| EV charger (Level 2) | 40A @ 240V | 8 AWG | 10 mm² | Continuous EV loads often use 125% → 50 A; 75°C column screen ≈ 8 AWG when markings allow |
| 10 HP motor @ 480V 3φ | FLC ≈ 14A (NEC Art. 430 tables) | 12 AWG | 4 mm² | Prefer Motor Cable Size for 125% FLC + VD; VFD installs need separate checks |
| Main panel feed (100A) | 100A @ 240V | 3 AWG | 25 mm² | 75°C Cu screen ≈ 3 AWG / 100 A when terminations allow; 60°C basis may upsize — |
| Commercial lighting (20A circuit) | 20A @ 120/208V 3φ | 12 AWG | 4 mm² | Common 20 A branch pairing; confirm adopted small-conductor/OCPD limits |
| Industrial feeder (200A) | 200A @ 480V 3φ | 3/0 AWG | 85 mm² | 75°C Cu screen ≈ 3/0; parallel sets for larger feeders are not modeled here |
Voltage Drop Calculation Example
When cable runs are long, voltage drop often governs the size—not ampacity. Informational notes in many NEC editions mention about 3% on a branch and 5% feeder + branch total as planning targets—not automatic pass/fail ampacity rules. Use the resistive formula for a quick screen:
Vd = 2 × L × I × R ÷ 1000 (single-phase) or Vd = √3 × L × I × R ÷ 1000 (3-phase), where L = one-way length in feet, I = current in amps, R = conductor resistance in Ω/1000ft.
Example: 50A load, 240V single-phase, 100 ft one-way
Step 1: Ampacity-only screen → 8 AWG (50 A @ 75°C column when terminations allow) or larger on the 60°C column before installation-condition checks.
Step 2: Voltage drop check — 8 AWG R = 0.778 Ω/1000ft gives 7.78 V (3.24%), above the 3% target; upsize to 6 AWG, where 4.91 V = 2.05% of 240 V.
If run were 200 ft: Vd = 9.82V = 4.1% → exceeds 3%. Upsize to 4 AWG (R = 0.308 Ω/1000ft → Vd = 6.16V = 2.57%).
For 3-phase loads, replace the factor of 2 with √3 (1.732). For aluminum conductors, use ~1.6x the resistance of copper at the same AWG. Always confirm with manufacturer voltage drop tables for final design.
Installation method (why OEM tables still win)
Ampacity changes with how the cable is installed. Use Advanced Ca/Cg for a quick upsize; confirm final size on project IEC/NEC tables (Southwire/Eland-class tools encode these factors in brand software—we stay method-agnostic for planning).
| Install method | Planning note |
|---|---|
| In conduit / raceway | Higher ambient + fill → apply Ca and count conductors for Cg |
| Cable tray | Grouping and layering often force one mm² step up |
| Buried / duct bank | Soil thermal resistivity dominates—use project tables, not this screen alone |
| Free air | Often highest ampacity; still check VD on long outdoor runs |
Use the suggested mm² as an early BOM or panel schedule checkpoint, then validate against detailed manufacturer tables including ambient, installation method, and voltage drop along the route.
Next step after screening: combine your candidate size with breaker frames and source ratings using the breaker size calculator, transformer size calculator, and generator size calculator, then confirm against IEC/NEC tables. Browse the protection calculators hub for the full lane.
Common standards designers cross-check
Cable sizing in practice is read against the locally adopted wiring rules and tabulated ampacity—for U.S. projects this page’s AWG screen is bound to NEC 2023 Table 310.16 (older editions used 310.15(B)(16)); elsewhere use IEC 60364, BS 7671, AS/NZS 3008, or manufacturer tables. The mm² output is an IEC 60228-style ladder for early screening, not a full IEC ampacity selection for installation method.
NEC / AWG cross-check for US projects
After you have a candidate mm², map to approximate AWG/kcmil and confirm allowable amps under the adopted NEC edition (temperature rating, ambient, bundling, small-conductor/OCPD limits, and whether parallel conductors apply). The AWG screen on this page uses NEC 2023 Table 310.16 columns selected in Advanced; it still does not size parallel sets.
| Screening mm² (Cu) | Approx. AWG | Illustrative NEC 2023 Cu screen (60°C / 75°C) | Load |
|---|---|---|---|
| 1.5 | 16 AWG | ~15 A / ~20 A | |
| 2.5 | 14 AWG | ~20 A / ~25 A | |
| 4 | 12 AWG | ~25 A / ~30 A | |
| 6 | 10 AWG | ~30 A / ~35 A | |
| 10 | 8 AWG | ~40 A / ~50 A | |
| 16 | 6 AWG | ~55 A / ~65 A | |
| 25 | 4 AWG | ~70 A / ~85 A | |
| 35 | 2 AWG | ~95 A / ~115 A · 100 A screen | |
| 50 | 1 AWG | ~110 A / ~130 A | |
| 70 | 2/0 AWG | ~145 A / ~175 A | |
| 95 | 3/0 AWG | ~165 A / ~200 A |
Quick PAA — what size wire for 100 amp service? At 240 V 1φ, many NEC 75°C Cu screens land near 3 AWG (use the 100 A panel · 240 V preset). At 480 V 3φ, screening often lands near 3 AWG Cu / 1 AWG Al (75°C) or ~35 mm² on the IEC ladder—always apply ambient/bundling and match OCPD with the breaker size calculator.
3-phase motor cable sizing (FLA screen)
Motors: take nameplate or NEC Table 430.250 FLA, apply continuous/branch factors from your code (often 125% of FLA for conductors), enter that design amps above for mm² screening, then map to AWG. Example: ~50 HP @ 460 V ≈ 65 A FLA → 65 × 1.25 ≈ 81 A → screening ladder often ~25 mm² / 4 AWG Cu before voltage drop and starting voltage dip—see motor starting & protection.
Last updated: 2026-09-13. mm² screening + AWG illustration only—not a reprint of NEC Table 310.16 or IEC 60364-5-52.
References
- NFPA 70 (NEC) — ampacity & wiring methods
- IEC TC 64 / IEC 60364 wiring overview
- Engineering Toolbox — AWG wire gauges
Installation method, grouping & fault current
Real ampacity depends on how the run is installed—for example in conduit, on cable tray, buried, or in free air—together with grouping/bundling and ambient temperature derating. Use Advanced Ca/Cg for a quick upsized screen; still confirm final ampacity on your IEC/NEC project tables.
Fault current & protection: available fault current, device let-through, and adiabatic thermal limits can require a larger conductor than steady-state ampacity. Size OCPD and check short-circuit withstand after screening—see the breaker size calculator and motor starting & protection guide for coordination context.
More context: Voltage drop calculation · kW to kVA Formula Explained · 3-Phase Power Calculator · When to Use kVA Instead of kW
3-phase cable size chart (kW → A → mm² / AWG)
Screening look-up at PF 0.85 copper, underrated (Ca = Cg = 1). Line current Ib = P ÷ (√3 × V × PF). AWG is an approximate NEC cross-check only. Enter the same kW in the calculator (From kW) or apply Advanced derating when ambient/grouping apply.
| Load (kW) | Ib @ 400 V (A) | mm² / AWG @ 400 V | Ib @ 480 V (A) | mm² / AWG @ 480 V |
|---|---|---|---|---|
| 15 | 25.5 | 4 / 12 AWG | 21.2 | 4 / 12 AWG |
| 22 | 37.4 | 6 / 10 AWG | 31.1 | 6 / 10 AWG |
| 30 | 51.0 | 10 / 8 AWG | 42.5 | 10 / 8 AWG |
| 37 | 62.8 | 16 / 6 AWG | 52.4 | 10 / 8 AWG |
| 45 | 76.5 | 25 / 4 AWG | 63.7 | 16 / 6 AWG |
| 55 | 93.5 | 25 / 4 AWG | 77.8 | 25 / 4 AWG |
| 75 | 127.4 | 35 / 2 AWG | 106.2 | 35 / 2 AWG |
| 100 | 169.9 | 50 / 1 AWG | 141.6 | 50 / 1 AWG |
After screening, check long feeders on the voltage drop calculator and OCPD on the breaker size calculator.
Frequently Asked Questions
How do I size solar / PV DC cable?
Compute array current from module Isc × parallel strings (see series-parallel), apply your code’s continuous-current factor (often 1.25× on Isc), enter that design amps here for mm² screening, then check DC voltage drop on long runs. Example: Isc 11 A × 2P × 1.25 = 27.5 A → use the PV DC string Quick preset or jump to #solar-dc-cable—often screens near ~6 mm² / ~10 AWG before derating. Hub: Solar calculators hub—no separate solar-DC-only cable page.
How do I size 12 V battery or inverter DC cable?
Enter continuous DC amps (or click the 12 V battery / 48 V inverter preset), set Phase to DC (2-wire) and voltage to 12/24/48. Read the NEC-style AWG screen and IEC mm², enter one-way length in feet under Advanced, then check 12 V / DC voltage drop—percent loss is much higher than on 120 V AC for the same gauge.
Is this a wire gauge length calculator?
Ampacity (AWG/mm²) comes from design current. Enter one-way length under Advanced and choose a 3% or 5% VD planning limit to upsize AWG/mm² when the resistive screen exceeds the target (ampacity + drop on one page). Still open NEC voltage drop for the full K-method check—or use the % drop table for a quick 20 A look-up.
Is this a wire gauge calculator / wire size calculator?
Yes. Enter design amps (or kW) to screen mm², then use the AWG/NEC cross-check for approximate wire gauge. Optional Advanced length + 3%/5% couples voltage-drop upsizing on the same screen. The same tool covers 3-phase cable size, DC / 12 V / battery / inverter cable screening, and VFD feeder ampacity.
What is a cable size calculator?
A cable size calculator screens IEC-style mm² from design amps and conductor material (Cu/Al). Example: 32 A copper → 6 mm² on the screening ladder—then apply derating and check voltage drop on long runs.
How do I calculate 3 phase cable size?
To calculate 3 phase cable size, enter From kW with PF and voltage (Ib = P ÷ (√3 × V × cos φ)), or enter design amps directly. Then screen the next standard mm² from this calculator’s IEC-style ladder, optionally apply Advanced Ca/Cg derating, and verify voltage drop on the actual run length.
How do bundled cables affect ampacity?
Grouped conductors reduce heat dissipation, so tabulated ampacity must be multiplied by a grouping derating factor from IEC 60364 or NEC tables. Use Advanced → Grouping correction Cg for a quick upsized screen (It = Ib ÷ (Ca × Cg)), then confirm on your project tables.
What ambient temperature derating should I apply?
Use the correction factor from your wiring code for the conductor insulation rating (for example 70 °C or 90 °C PVC/XLPE) and the expected ambient—or pick an illustrative Ca under Advanced. High ambient or enclosed trays often push you one mm² step—or more—above a current-only screening value.
When does fault current require a larger conductor?
Short-circuit thermal limits (adiabatic withstand) can force a larger cross-section than steady-state ampacity. Check available fault current, protection device let-through, and manufacturer k²S² limits—use the breaker size calculator and project fault studies after screening mm² here.
Can you provide a cable sizing example with numbers?
Given: 37 kW, PF 0.85, 400 V three-phase → kVA ≈ 43.5, line current I ≈ 63 A. Screening ladder → 16 mm² Cu. Then verify grouping derating and route voltage drop before locking the BOM.
How does mm² relate to AWG for NEC projects?
IEC 60228 uses metric mm²; NEC projects often specify AWG/kcmil. Approximate cross-checks: 6 mm² ≈ 10 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG, 70 mm² ≈ 2/0 AWG—see the NEC / AWG cross-check table. Always confirm against NEC Table 310.16 (or your adopted edition) for insulation and installation method.
What size cable for 100 A at 480 V three-phase?
As a screening illustration, ~100 A continuous at 480 V 3-phase often lands near 3 AWG Cu (75 °C) or 1 AWG Al on many NEC ampacity readings—or ~35 mm² on this page’s IEC-style ladder before derating. Apply ambient/bundling corrections and match OCPD; use the calculator with 100 A design current.
How do I size cable for a 3-phase motor?
Use motor FLA (nameplate or NEC 430.250), apply your code’s conductor factor (often 125% of FLA), enter that amps above for mm², then map to AWG. Example: ~50 HP @ 460 V ≈ 65 A FLA → ~81 A → often ~25 mm² / 4 AWG Cu before voltage-drop checks. See motor cable sizing.
How do harmonics affect cable sizing?
Non-linear loads add harmonic current that increases conductor heating and neutral loading. Derating or upsizing may be required beyond a fundamental-frequency ampacity check—this page assumes steady-state RMS design current only.
What is the difference between copper and aluminum cables?
Copper has higher conductivity, so it carries more current for the same cross-section and is more compact, but more expensive. Aluminum is lighter and cheaper but often requires a larger cross-section and special terminations.
How does voltage drop affect cable sizing?
Long runs at high current can cause significant voltage drop. In many standards you must keep voltage drop below a specified percentage, which may require a larger cable than indicated by current capacity alone—use the voltage drop calculator after screening.
What standards do engineers cross-check for cable sizing?
Designers cross-check IEC 60364, NEC ampacity chapters, BS 7671, or AS/NZS 3008 plus manufacturer data for insulation temperature rating. This tool does not replace those tables or statutory compliance.
Where is the cable size chart?
Use the cable size chart (amps → AWG / mm²) below the results, or the 3-phase kW chart. For 12 V / battery DC, pick the battery preset, set DC 2-wire, then read AWG from the same chart—voltage drop often forces upsizing on long runs.
Ampacity chart vs voltage-drop path—what do I do after the chart?
The ampacity chart screens AWG/mm² from design current. After that chart step, verify long runs on the voltage drop calculator—drop limits often force a larger conductor than ampacity alone. For OCPD and protection workflow, continue on the Protection calculator hub.
Do you have a conduit sizing for wire calculator?
No dedicated conduit-fill tool. Size the conductor here first, then select raceway trade size from NEC Chapter 9 Annex C (or manufacturer fill). See conduit note—ampacity in conduit still needs Ca/Cg derating.
Does the calculator change results by installation method (conduit, tray, buried)?
Optionally. Use Advanced Ca (ambient) and Cg (grouping) to inflate the screening current. Real ampacity still depends on installation method (conduit, cable tray, buried, or free air); confirm correction factors on your project tables after you have a candidate mm².
Is this calculator suitable for final design?
No. It is intended for quick checks and concept design. Final cable selection must follow detailed tables from standards and manufacturers, and should be validated by a qualified electrical engineer.
Related Tools
- Voltage Drop Formula & Calculator (1φ/3φ/DC, Instant)
- Circuit Breaker Size Calculator
- EV Charger Load Calculator (Instant Breaker & Amps)
- Available Fault Current Calculator
- 3 Phase Power Calculator (Instant, Free) — Electrical Formulas
- kW to kVA Calculator (Instant, Free, with Formula & Examples)
- kVA to Amps Calculator (Instant, Free) — Also Amps to kVA
- Generator Wattage Calculator