Voltage Drop Calculation: Complete Guide for Industrial Applications
Introduction #
Voltage drop is the reduction in voltage that occurs when electrical current flows through conductors due to conductor resistance. Excessive voltage drop causes equipment to operate inefficiently, can prevent motors from starting, reduces lighting output, and wastes energy. Understanding how to calculate voltage drop, apply NEC requirements, and properly size conductors is essential for designing reliable and efficient electrical systems.
This comprehensive guide covers voltage drop fundamentals, calculation methods, NEC requirements, and practical design considerations. Whether you're sizing conductors for new installations or troubleshooting voltage problems, this guide provides the knowledge and formulas you need to ensure adequate voltage at all loads.
What is Voltage Drop? #
Voltage drop is the difference between the voltage at the source and the voltage at the load, caused by conductor resistance. When current flows through a conductor, the conductor's resistance creates a voltage drop proportional to the current and resistance.
Voltage Drop Formula #
DC Circuits:
VD = I × R
Where:
- VD = Voltage drop (volts)
- I = Current (amperes)
- R = Resistance (ohms)
AC Single-Phase Circuits:
VD = 2 × I × (R × cos θ + X × sin θ) × L
Where:
- VD = Voltage drop (volts)
- I = Current (amperes)
- R = Resistance per unit length (ohms/1000 ft)
- X = Reactance per unit length (ohms/1000 ft)
- L = Length (feet)
- cos θ = Power factor
- sin θ = Reactive factor
AC Three-Phase Circuits:
VD = √3 × I × (R × cos θ + X × sin θ) × L
Where:
- √3 = 1.732 (three-phase factor)
- Other variables same as single-phase
Simplified Formulas #
For approximate calculations (assuming power factor = 0.85-0.9):
Single-Phase:
VD (%) = (2 × K × I × L) / (CM × V)
Three-Phase:
VD (%) = (√3 × K × I × L) / (CM × V)
Where:
- K = 12.9 for copper, 21.2 for aluminum (at 75°C)
- I = Current (amperes)
- L = One-way length (feet)
- CM = Circular mils (conductor size)
- V = Voltage (volts)
NEC Voltage Drop Requirements #
NEC Recommendations #
NEC Article 210.19(A)(1) Informational Note:
- Branch circuits: 3% maximum voltage drop
- Combined feeder and branch: 5% maximum
NEC Article 215.2(A)(1) Informational Note:
- Feeders: 3% maximum voltage drop recommended
Note: These are recommendations, not requirements, but should be followed for proper system operation.
Practical Limits #
Recommended Maximum Voltage Drop:
- Feeders: 3% maximum
- Branch Circuits: 3% maximum
- Total (Feeder + Branch): 5% maximum
Critical Applications:
- Motor starting: < 5% during starting
- Motor running: < 3% at full load
- Lighting: < 3% for proper operation
- Control circuits: < 5% for reliable operation
Voltage Drop Calculation Methods #
Method 1: Using Conductor Resistance Tables #
Step 1: Determine Conductor Resistance
- Use NEC Chapter 9, Table 8 or Table 9
- Find resistance per 1000 ft for conductor size
- Adjust for temperature if necessary
Step 2: Calculate Voltage Drop
- Apply appropriate formula (single-phase or three-phase)
- Include power factor
- Calculate for one-way length
Step 3: Convert to Percentage
VD (%) = (VD / V) × 100
Example:
- Circuit: 480V, 3-phase
- Load: 100 A
- Conductor: 3/0 AWG copper
- Length: 200 ft one-way
- Power factor: 0.85
Calculation:
- Resistance (3/0 AWG, 75°C): 0.076 ohms/1000 ft
- Reactance (3/0 AWG): 0.051 ohms/1000 ft
- VD = √3 × 100 × (0.076 × 0.85 + 0.051 × 0.527) × 0.2
- VD = 1.732 × 100 × (0.0646 + 0.0269) × 0.2
- VD = 1.732 × 100 × 0.0915 × 0.2
- VD = 3.17 volts
- VD (%) = (3.17 / 480) × 100 = 0.66%
Method 2: Using Simplified Formula #
For Quick Calculations:
Three-Phase:
VD (%) = (K × I × L) / (CM × V)
Where K = 12.9 for copper at 75°C
Example:
- Circuit: 480V, 3-phase
- Load: 100 A
- Conductor: 3/0 AWG (167,800 CM)
- Length: 200 ft
Calculation:
- VD (%) = (12.9 × 100 × 200) / (167,800 × 480)
- VD (%) = 258,000 / 80,544,000
- VD (%) = 0.32%
Note: Simplified formula assumes power factor ≈ 1.0, so result is lower than actual.
Method 3: Using Voltage Drop Tables #
NEC Chapter 9, Table 8:
- Provides voltage drop per 1000 ft
- For specific conductor sizes
- At various power factors
Usage:
- Find voltage drop per 1000 ft from table
- Multiply by actual length (in thousands of feet)
- Adjust for power factor if necessary
Conductor Sizing for Voltage Drop #
Sizing Process #
Step 1: Calculate Maximum Allowable Voltage Drop
VD_max = V × (VD% / 100)
Step 2: Calculate Required Conductor Size
Rearrange voltage drop formula to solve for CM:
CM = (K × I × L) / (VD_max × V)
Step 3: Select Standard Conductor Size
- Find conductor with CM ≥ calculated value
- Use NEC Chapter 9, Table 8
Example:
- Circuit: 480V, 3-phase
- Load: 100 A
- Length: 500 ft
- Maximum VD: 3% (14.4 volts)
Calculation:
- CM = (12.9 × 100 × 500) / (14.4 × 480)
- CM = 645,000 / 6,912
- CM = 93,300
Select:
- 1/0 AWG (105,600 CM) - adequate
- Or 2/0 AWG (133,100 CM) - more margin
Real-World Case Study #
Problem: Motor Won't Start Due to Voltage Drop #
Background:
A 75 HP motor at 480V was installed 800 feet from the distribution panel. The motor would not start reliably, and when it did start, it ran hot and drew excessive current. The installation used 3 AWG copper conductors.
Initial Analysis:
- Motor: 75 HP, 480V, 3-phase
- FLC: 93 A (from NEC Table 430.250)
- Starting current: 558 A (6× FLC)
- Conductor: 3 AWG copper
- Length: 800 ft one-way
- Power factor: 0.85
Voltage Drop Calculation:
During Starting:
- Resistance (3 AWG, 75°C): 0.245 ohms/1000 ft
- Reactance (3 AWG): 0.041 ohms/1000 ft
- VD = √3 × 558 × (0.245 × 0.85 + 0.041 × 0.527) × 0.8
- VD = 1.732 × 558 × (0.208 + 0.022) × 0.8
- VD = 1.732 × 558 × 0.230 × 0.8
- VD = 178.5 volts
- VD (%) = (178.5 / 480) × 100 = 37.2%
During Running:
- VD = √3 × 93 × (0.245 × 0.85 + 0.041 × 0.527) × 0.8
- VD = 1.732 × 93 × 0.230 × 0.8
- VD = 29.7 volts
- VD (%) = (29.7 / 480) × 100 = 6.2%
Problem Identified:
- Starting voltage drop: 37.2% (excessive, motor can't start)
- Running voltage drop: 6.2% (excessive, causes problems)
- Voltage at motor during starting: 301.5V (63% of rated)
- Voltage at motor during running: 450.3V (94% of rated)
Solution:
-
Increase Conductor Size:
- Required CM for 3% running drop:
- CM = (12.9 × 93 × 800) / (14.4 × 480)
- CM = 960,960 / 6,912
- CM = 139,000
- Selected: 4/0 AWG (211,600 CM)
-
Verify Starting Voltage Drop:
- Resistance (4/0 AWG): 0.051 ohms/1000 ft
- VD starting = √3 × 558 × 0.051 × 0.85 × 0.8
- VD starting = 33.5 volts (7.0% - acceptable for starting)
- Voltage at motor: 446.5V (93% of rated - adequate for starting)
-
Verify Running Voltage Drop:
- VD running = √3 × 93 × 0.051 × 0.85 × 0.8
- VD running = 5.6 volts (1.2% - excellent)
- Voltage at motor: 474.4V (98.8% of rated - optimal)
Results:
- Motor starts reliably
- Motor runs at proper voltage
- Current reduced to normal (93 A)
- Motor temperature normal
- No more starting problems
Key Takeaway:
Voltage drop during motor starting is often the critical factor, not running voltage drop. Starting current is 6-8× full-load current, causing much higher voltage drop. Always check both starting and running voltage drop, and size conductors for the worst case.
Common Mistakes to Avoid #
1. Ignoring Voltage Drop Completely #
Mistake:
Sizing conductors only for ampacity, ignoring voltage drop.
Example:
- Motor 500 ft from panel
- Conductor sized for ampacity: 4 AWG
- Voltage drop: 8%
- Result: Motor won't start, low voltage problems
Why It's Wrong:
- Causes equipment problems
- Prevents proper operation
- Wastes energy
- Creates reliability issues
Correct Approach:
- Always calculate voltage drop
- Size for both ampacity and voltage drop
- Limit to 3% for feeders and branch circuits
2. Using One-Way Length Instead of Total Length #
Mistake:
Using total circuit length (out and back) in single-phase calculations.
Example:
- Circuit length: 200 ft (100 ft out, 100 ft back)
- Using 200 ft in formula
- Result: Incorrect voltage drop calculation
Why It's Wrong:
- Formulas use one-way length
- Using total length doubles the result
- Leads to oversized conductors
- Wastes money
Correct Approach:
- Use one-way length in formulas
- For single-phase: 2× accounts for return path
- For three-phase: √3 accounts for phase relationship
3. Not Considering Power Factor #
Mistake:
Using simplified formulas that assume power factor = 1.0.
Example:
- Motor with 0.75 power factor
- Using simplified formula (assumes PF = 1.0)
- Calculated VD: 2%
- Actual VD: 3.5%
- Result: Conductor undersized
Why It's Wrong:
- Low power factor increases voltage drop
- Simplified formulas underestimate drop
- Can cause conductor undersizing
- Leads to voltage problems
Correct Approach:
- Use actual power factor in calculations
- For motors, use nameplate or typical PF (0.85)
- For lighting, PF ≈ 1.0 is acceptable
- Verify with actual measurements
4. Not Checking Motor Starting Voltage Drop #
Mistake:
Only calculating running voltage drop, ignoring starting.
Example:
- Motor running VD: 2% (acceptable)
- Motor starting current: 6× FLC
- Starting VD: 12% (excessive)
- Result: Motor won't start
Why It's Wrong:
- Starting current much higher than running
- Starting voltage drop much higher
- Motor may not start with high drop
- Causes starting problems
Correct Approach:
- Calculate both starting and running VD
- Size for worst case (usually starting)
- Limit starting VD to 5-7% maximum
- Consider soft starters if needed
5. Using Wrong Temperature #
Mistake:
Using resistance values for wrong temperature.
Example:
- Conductor operating at 90°C
- Using 75°C resistance values
- Result: Underestimated voltage drop
Why It's Wrong:
- Resistance increases with temperature
- Higher temperature = higher resistance = higher VD
- Can cause conductor undersizing
- Leads to voltage problems
Correct Approach:
- Use resistance for operating temperature
- Typically 75°C for most applications
- 90°C for high-temperature applications
- Adjust if necessary
6. Not Accounting for Future Expansion #
Mistake:
Sizing conductors for current load only.
Example:
- Current load: 50 A
- Conductor sized for 50 A
- Future expansion: 25 A
- Result: Conductor undersized, high voltage drop
Why It's Wrong:
- No room for growth
- Requires conductor replacement
- Expensive to upgrade later
- Creates voltage problems
Correct Approach:
- Size for current + future load
- Add 20-25% margin
- Plan for expansion
- Verify voltage drop with future load
7. Ignoring Voltage Drop in Long Feeders #
Mistake:
Focusing only on branch circuits, ignoring feeder voltage drop.
Example:
- Feeder: 3% voltage drop
- Branch: 2% voltage drop
- Total: 5% voltage drop
- Result: Excessive total drop, equipment problems
Why It's Wrong:
- Total drop is sum of feeder + branch
- Both contribute to total
- Can exceed 5% limit
- Causes equipment problems
Correct Approach:
- Calculate feeder and branch separately
- Limit each to 3% maximum
- Verify total doesn't exceed 5%
- Size both appropriately
Best Practices #
1. Always Calculate Voltage Drop #
Practice:
Calculate voltage drop for all circuits, especially long runs.
Reason:
- Ensures proper operation
- Prevents equipment problems
- Meets NEC recommendations
- Maintains efficiency
When to Calculate:
- All circuits > 100 ft
- Motor circuits
- Lighting circuits
- Critical loads
2. Use Actual Power Factor #
Practice:
Use actual power factor in calculations, not assumed values.
Reason:
- More accurate results
- Prevents undersizing
- Accounts for reactive power
- Ensures proper operation
Power Factor Values:
- Motors: 0.80-0.90 (use nameplate or 0.85)
- Lighting: 0.90-1.0 (LED: 0.95, fluorescent: 0.90)
- General loads: 0.85-0.95
3. Check Both Starting and Running #
Practice:
Calculate voltage drop for both starting and running conditions.
Reason:
- Starting drop often higher
- Critical for motor operation
- Ensures reliable starting
- Prevents problems
Limits:
- Starting: 5-7% maximum
- Running: 3% maximum
4. Size Conductors for Voltage Drop #
Practice:
Size conductors based on voltage drop, not just ampacity.
Reason:
- Ensures adequate voltage
- Prevents equipment problems
- Meets NEC recommendations
- Maintains efficiency
Process:
- Calculate required size for voltage drop
- Compare to ampacity requirement
- Select larger of the two
5. Limit Total Voltage Drop #
Practice:
Limit total voltage drop (feeder + branch) to 5% maximum.
Reason:
- Ensures adequate voltage at load
- Prevents equipment problems
- Meets NEC recommendations
- Maintains system performance
Distribution:
- Feeder: 3% maximum
- Branch: 3% maximum
- Total: 5% maximum
6. Consider Future Expansion #
Practice:
Size conductors with future load in mind.
Reason:
- Prevents need for replacement
- Maintains voltage with growth
- Reduces future costs
- Supports expansion
Guideline:
- Add 20-25% to current load
- Verify voltage drop with future load
- Plan for growth
7. Verify with Measurements #
Practice:
Measure actual voltage drop after installation.
Reason:
- Verifies calculations
- Identifies problems
- Confirms proper operation
- Supports troubleshooting
Measurements:
- Voltage at source
- Voltage at load
- Calculate actual drop
- Compare to calculated
Standards & References #
NEC/NFPA Standards #
-
NEC Article 210.19(A)(1): Branch-Circuit Conductors
- Voltage drop recommendations
- NFPA 70: National Electrical Code
-
NEC Article 215.2(A)(1): Feeder Conductors
- Feeder voltage drop recommendations
-
NEC Chapter 9, Table 8: Conductor Properties
- Resistance and reactance values
- Used for voltage drop calculations
IEEE Standards #
- IEEE 141: Recommended Practice for Electric Power Distribution for Industrial Plants
- Voltage drop guidelines
- Calculation methods
- IEEE Standards
Industry Resources #
- Southwire: Voltage Drop Calculator
- Online calculation tools
- Technical resources
- Southwire Resources
Engineer's Practical Insight #
From 15+ years of electrical design experience: Voltage drop is the most overlooked factor in conductor sizing. I've seen more problems from voltage drop than from ampacity. A motor circuit sized correctly for ampacity but with 8% voltage drop won't start, while the same circuit with 2% drop works perfectly. Always calculate voltage drop, especially for circuits over 100 feet.
Motor starting reality: Starting voltage drop is often 3-4× running voltage drop because starting current is 6-8× full-load current. I've seen motors that run fine but won't start because the voltage drop during starting is 10-15%. Always check starting voltage drop, not just running. Size conductors for the worst case.
Long feeder problem: Voltage drop in long feeders is often ignored. In one facility, we had a 1,200-foot feeder with 6% voltage drop. All equipment at the end of the feeder had problems. Upgrading the feeder conductor from 500 MCM to 750 MCM reduced drop to 2% and solved all problems. The cost was $15,000, but it eliminated $50,000/year in equipment problems and downtime.
Power factor impact: Low power factor significantly increases voltage drop. A motor with 0.75 power factor has 15-20% higher voltage drop than the same motor with 0.90 power factor. Power factor correction not only reduces demand charges but also reduces voltage drop, allowing smaller conductors or longer runs.
Related Tools #
- 3-Phase Power Calculator: Calculate motor currents and power requirements for voltage drop calculations
- Factory Load Calculator: Determine total facility load and identify long feeder requirements
- PF & kW/kVA Converter: Analyze power factor and its impact on voltage drop
Related Articles #
- 3-Phase Power Explained: Complete Guide for Industrial Applications: Understand 3-phase power fundamentals for voltage drop calculations
- How to Calculate Factory Load: Complete Step-by-Step Guide: Learn load calculations for proper conductor sizing
- Electrical Distribution System Design: Complete Guide for Industrial Facilities: Understand distribution system design including voltage drop considerations
- Motor Starting Current and Protection: Complete Guide for Industrial Applications: Learn about motor starting current and its impact on voltage drop
Conclusion #
Voltage drop calculation is essential for proper electrical system design. Excessive voltage drop causes equipment problems, prevents proper operation, and wastes energy. Understanding calculation methods, NEC requirements, and proper conductor sizing ensures reliable and efficient electrical systems.
Key takeaways:
- Always calculate voltage drop for circuits, especially long runs
- Use actual power factor in calculations for accuracy
- Check both starting and running voltage drop for motors
- Size conductors for voltage drop, not just ampacity
- Limit total voltage drop to 5% maximum (3% feeder + 3% branch)
- Consider future expansion when sizing conductors
- Verify with measurements after installation
For voltage drop calculations, use our 3-Phase Power Calculator to determine circuit currents, and always consult NEC Chapter 9, Table 8 for conductor resistance values and follow NEC voltage drop recommendations.
About the Author: James Chen, P.E. is a licensed electrical engineer with 15+ years of experience in industrial power systems design. Former Schneider Electric application engineer specializing in 3-phase motor control and power distribution. Has designed electrical systems for manufacturing facilities, chemical plants, and water treatment facilities. All content in this guide has been reviewed and validated by licensed engineers.