Battery Run Time Calculator
Estimate 12V battery run time from Ah and watts—100 Ah at 12 V and 200 W lasts about 6 hours. Not a UPS inverter model.
Calculator
Quick: Ah + load amps → hours. Advanced: mAh/Wh, watts load, DoD, efficiency, or reverse Ah sizing.
About this calculator
This battery run time calculator (also called a battery runtime calculator or battery life calculator) estimates hours for a DC pack, including 12V Ah and watt loads. It is not an APC/Eaton UPS selector and not a multi-day solar autonomy tool. For UPS inverter packs use UPS runtime; for Ah procurement use UPS battery sizing. Browse the power calculator hub.
Calculation Results
≈ 20.00 hours (20 h)
100 Ah · 5 A · DoD 1.00 · η 1.00
Formula: hours = (Ah × DoD × η) ÷ I
Assumptions: constant average load; Peukert / high C-rate capacity loss is not modeled (real hours can be shorter than this screen). Temperature and pulsed loads also matter—treat as planning only.
Continue Your Calculation
Need amp-hours for a target run time instead of hours? Switch to required Ah on this calculator.
UPS inverter minutes: UPS runtime calculator.
12V battery run time examples
How long does a 12V battery last?
For a 12 V pack, hours ≈ (Ah × 12 × DoD × η) ÷ watts. At DoD 1.0 and η 1.0, a 7 Ah battery at 1 A lasts 7 hours, and a 100 Ah battery at 200 W lasts 6 hours. A 200 Ah battery at 12 V and 200 W lasts 12 hours on that ideal path; with LiFePO4 DoD 0.8 and η 0.95 the same load lasts 9.12 hours.
Ideal hours at DoD 1.0 and η 1.0 (no Peukert). Open a row to load the calculator.
| Pack | Load | Ideal runtime |
|---|---|---|
| 1 A | 7 h | |
| 5 A | 20 h | |
| 200 W | 6 h | |
| 200 W | 12 h | |
| 200 W · DoD 0.8 | 9.12 h | |
| 200 W · DoD 0.8 | ≈ 4.6 h | |
| 200 W | 12 h | |
| 500 W · DoD 0.8 | ≈ 7.3 h | |
| 100 mA | 20 h |
Battery run time formula & explanation
hours = (Ah × DoD × η) ÷ I
With a watt load: hours = (Ah × V × DoD × η) ÷ W (same as converting W to amps with I = W ÷ V).
Peukert note: This calculator uses a linear energy balance (like DigiKey/Omni capacity ÷ current screens with a safety/DoD factor). It does not apply Peukert’s law—high discharge rates reduce available Ah, so field runtime can be shorter.
- Ah — amp-hour capacity (mAh ÷ 1000; Wh ÷ V).
- DoD — usable fraction of nameplate capacity (chemistry presets above).
- η — DC path / converter efficiency (≤ 1).
- I / W — average load current or power.
Example: 100 Ah, 12 V, 60 W, DoD 1.0, η 1.0 → I = 5 A → 20 hours.
Wh ↔ Ah converter: ampere hour to watt hour calculator. Ah ÷ hours → A: Ah to amps calculator. Solar multi-day bank sizing: solar battery bank / autonomy. UPS minutes: UPS runtime calculator.
When to use which battery tool
| Goal | Tool |
|---|---|
| DC pack hours from Ah / V / load | This page — battery runtime |
| UPS backup minutes (inverter + kVA) | UPS runtime calculator |
| Required Ah for UPS target minutes | UPS battery sizing |
| Series/parallel string layout | UPS battery bank |
| Solar days of autonomy (kWh) | Solar battery bank calculator |
What moves runtime beyond the entered DoD and efficiency
The calculator applies the usable depth of discharge and the path efficiency you enter. Four further factors explain why a measured runtime usually lands below the arithmetic result — they are the reason a nameplate amp-hour figure is a starting point, not an answer.
| Factor | Effect on usable runtime | Planning step |
|---|---|---|
| Depth of discharge vs cycle life | Cycling deeper buys runtime per discharge but consumes the service life faster: a 50% DoD duty typically yields a multiple of the cycles available at 80% DoD on the same cell. | Pick the DoD from the replacement interval you can actually service, not from the longest single discharge. |
| Temperature | Nameplate capacity is quoted near 25 °C. Cold cells deliver less of it on the same load, and sustained heat above the reference accelerates capacity fade. | Use the manufacturer's temperature-correction table for the coldest expected room, and treat a hot battery room as a life-reduction issue. |
| Discharge rate (hour-rate rating) | Rated amp-hours are stated at a reference hour rate (C20 is common for lead-acid blocks). Drawing the same bank faster than its reference rate delivers fewer amp-hours. | Read the vendor hour-rate table at your actual discharge time instead of scaling the C20 rating linearly. |
| Ageing / end of life | End of life is normally declared at a fraction of rated capacity (often 80%), so an aged bank reaches the calculated hours before the fresh-bank result. | Size on the end-of-life capacity you are willing to accept, then check interim years with a discharge test. |
The full derating treatment — vendor-style tables, depth-of-discharge and temperature modules — is in the UPS battery calculator. For what capacity fade does to runtime over the service life, see the UPS battery aging guide.
Frequently Asked Questions
How do I calculate battery runtime?
Hours ≈ (Ah × DoD × η) ÷ I. With watts: hours ≈ (Ah × V × DoD × η) ÷ W. Example: 100 Ah at 12 V into 60 W ≈ 20 hours at ideal DoD/η.
How long will a 100Ah battery last with a 200W load?
At 12 V ideal: hours ≈ (100 × 12) ÷ 200 = 6 hours. With LiFePO4 planning DoD 0.8 and η 0.95 ≈ 4.6 hours. Use the 100 Ah · 12 V · 200 W or LiFePO4 quick example above. At 24 V the same 100 Ah lasts about twice as long at the same watts.
How many hours is a 200Ah battery?
At 12 V and 200 W, ideal hours ≈ (200 × 12) ÷ 200 = 12 hours. With LiFePO4 DoD 0.8 and η 0.95 the same load lasts (200 × 12 × 0.8 × 0.95) ÷ 200 = 9.12 hours. At 100 W the ideal runtime is about 24 hours. Open the 12 V · 200 Ah row above to load this case. This is a DC energy balance, not a UPS inverter model.
How do I calculate 12V battery run time?
Hours ≈ (Ah × 12 × DoD × η) ÷ watts. Example: 100 Ah at 200 W, DoD 1.0 and η 1.0 = 6 hours. A 7 Ah battery at 1 A lasts 7 hours. Enter 12 V above, or use the 12 V preset.
Is this a lithium / LiFePO4 battery runtime calculator?
Yes for DC packs—enter Ah, V, and load. Use DoD ≈ 0.8–0.9 for many LiFePO4 packs (shallower than lead-acid 0.5). It is still an energy-balance screen, not a BMS or Peukert model.
Is this a battery life calculator?
Yes. Battery life and battery runtime here mean how long a DC pack can power a constant load. Enter Ah/mAh/Wh and A/mA/W above.
Is this a battery run time calculator or battery backup calculator?
Yes for DC packs. Battery run time calculator and DC-oriented battery backup calculator searches map here (Ah × V ÷ W with DoD/η). If you mean UPS wall/inverter backup minutes, switch to the UPS runtime calculator.
How is this different from a UPS runtime calculator?
This page is a DC energy-balance screen. The UPS runtime calculator models inverter efficiency, UPS kVA headroom, and OEM-oriented backup minutes.
How do I convert Wh to Ah?
Ah = Wh ÷ V. Example: 120 Wh at 12 V = 10 Ah. Use the dedicated ampere hour to watt hour calculator, or select Wh as capacity unit here and enter voltage.
How do I calculate battery runtime from capacity and average current?
Hours ≈ (Ah × DoD × η) ÷ I—the same capacity ÷ average current idea used on DigiKey-style battery life screens, plus optional DoD/η. Example: 100 Ah ÷ 5 A ≈ 20 hours at DoD 1.0. Peukert is not modeled.
Does depth of discharge change runtime?
Yes. Usable Ah ≈ nameplate × DoD. At DoD 0.5, planned hours are about half the DoD 1.0 ideal case before other losses. Use the chemistry presets (lead-acid / LiFePO4) to seed DoD, then fine-tune.
Related Tools
- UPS Runtime Calculator
- UPS Battery Calculator
- Ah to Watts & Wh Calculator (Free, 100 Ah = 1,200 W)
- Ah to Amps Calculator (Instant, Free) — Amp Hours to Amps
- UPS Battery Bank Calculator
- Solar Battery Bank Calculator (Instant, Free) — Battery Bank Size & kWh
- Industrial Energy Estimator
- Portable Power Station Size Calculator (Instant Wh & Watts)
Related Guides
- How to Calculate UPS Runtime — Runtime calculation with discharge curves and load factors
- How to Calculate UPS Battery Size — Battery bank sizing for required runtime
- UPS Battery Maintenance — Inspection, testing, and replacement criteria
- UPS Battery Aging & Runtime Degradation — How capacity fade affects runtime over time
- Home Battery Storage Sizing (kWh Formula & Examples) — How a kWh storage target turns into capacity, voltage and chemistry choices
Last updated: 2026-10-09. Planning estimate only—validate against the battery manufacturer's discharge tables before procurement.
Reviewed by: CalcPanel editorial team (mechanical engineers and technical editors).
References
- IEC 62619:2022 — safety requirements for secondary lithium cells and batteries in industrial applications (covers stationary / UPS duty)
- IEEE 485 — recommended practice for sizing lead-acid batteries for stationary applications
- IEEE 1188 — maintenance, testing and replacement of valve-regulated lead-acid (VRLA) batteries