Data Center Power Chain

One record from IT kW to rack density, PDU amps, UPS, and a step-down transformer frame. It does not replace those calculators.

Chain inputs

About this calculator

Uses the same balanced PDU current and UPS energy screen as the existing pages. Open PDU sizing for phase currents, UPS runtime for a full battery case, and step-down transformer sizing for the hall transformer. Hub: power calculators.

Result

Planning estimate. Confirm phase currents, battery runtime, and the transformer frame on the linked pages.

Assumptions: one balanced three-phase feed and one battery string when runtime is calculated. Generator capacity and rack cooling are not checked on this record.

Continue Your Calculation

Open UPS runtime for the battery case. Measured phase currents stay on the PDU sizing page. Generator and cooling stay on their existing pages.

What stays on existing pages

CheckWhere
Phase imbalancePDU sizing
GeneratorGenerator size
Cooling airflowRack cooling

Formula

I = kW × 1000 ÷ (√3 × V × PF) × (1 + margin). kW/rack = IT kW ÷ rack count. Example: 100 kW, 10 racks, 415 V, PF 0.95, 20% margin.

Worked example

100 kW across 10 racks is 10 kW/rack. The PDU line is the balanced current after margin. The transformer line is the next standard frame at or above planning kVA.

FAQ

Does this replace the PDU calculator?

No. Measured phase currents stay on the PDU sizing page.

Where is generator sizing?

Not checked here. Use the generator size calculator.

Where is rack cooling?

Not checked here. Use the rack cooling airflow page.