kW to kVAR Calculator

Convert kW and power factor to reactive power (kVAR) for motor loads and PF correction. Example: 10 kW @ PF 0.85 ≈ 6.19 kVAR lagging.

Calculator

Quick: kW presets and PF band. Advanced: switch direction to solve kW from a target kVAR.

Typical: motor 5–50 kW, plant block 100–500 kW

About this calculator

Estimates lagging reactive power (kVAR) from real power and PF using the power triangle—useful for capacitor bank screening and comparing against utility PF penalties. Part of the Power Calculator hub (featured topic).

Calculation Results

6.19kVAR
Default: 10 kW at PF 0.8511.76 kVA, 6.19 kVAR lagging.
Engineering disclaimer

Estimate only—harmonics, leading PF, and unbalance need site measurements. Final capacitor bank design requires engineering review.

kW to kVAR chart (PF 0.85, lagging)

kVAR = kW × tan(arccos PF) at PF 0.85. Open a row to load the calculator.

kWPFkVAkVAROpen
50.855.883.09Open
100.8511.766.19Open
250.8529.4115.47Open
500.8558.8230.95Open
1000.85117.6561.89Open

Formula & Explanation

For lagging loads: kVA = kW ÷ PF and kVAR = √(kVA² − kW²), equivalent to kVAR = kW × tan(arccos PF).

Example: 10 kW @ PF 0.85 → kVA = 11.76, kVAR = √(11.76² − 10²) ≈ 6.19 kVAR. At PF 0.80, the same 10 kW needs 7.50 kVAR—lower PF means more reactive power for the same real work.

See also kW to kVA, 3-phase power, and the power factor formula.

Learn About Power Factor

Understand power factor formulas, typical industrial values, correction methods, and utility penalty rules in our central topic guide.

Power Factor Guide →

Typical motor reactive power (PF 0.85)

LoadkWkVAR
Small motor7.54.64
Medium motor3018.57
Plant block200123.78

Frequently Asked Questions

How do I calculate capacitor bank size for power factor correction?

Find required kVAR with kVAR = √(kVA² − kW²) where kVA = kW ÷ PF. Example: 100 kW @ 0.85 PF needs ~62 kVAR correction to reach unity. Use this calculator, then see capacitor bank sizing guide.

What is PF penalty in an electricity bill?

Utilities charge when power factor falls below a threshold (often ~0.90–0.95). Low PF raises apparent power (kVA) and reactive demand. Estimate kVAR here, then read PF penalty rules & cost impact.

How do I convert kW to kVAR?

Find kVA = kW ÷ PF, then kVAR = √(kVA² − kW²). Example: 10 kW @ 0.85 PF → 6.19 kVAR. Use the calculator.

Is kVAR equal to kW?

No. kW is real power; kVAR is reactive. They match only at PF 1.0 when kVAR = 0.

What does a PF of 80% mean?

PF 0.80 means 80% of apparent power is real; the rest is reactive. 10 kW @ 0.80 PF → kVA 12.5, kVAR ≈ 7.5. Compare with 10 kW @ 0.80 PF preset.

What is kVAR vs kW?

kW does useful work; kVAR supports magnetic fields in motors and transformers. Utilities and capacitors care about kVAR for PF correction.

How much kVAR for 50 kW at 0.85 PF?

About 30.95 kVAR lagging (kVA ≈ 58.82). Open 50 kW preset.