Amps to kVA Calculator
Convert amps to kVA from line current, voltage, and phase—instant apparent power for generators, feeders, and transformers.
Formula: 1φ kVA = I × V ÷ 1000 · 3φ L-L kVA = √3 × I × V ÷ 1000. Example: 100 A @ 480 V 3φ ≈ 83.1 kVA. Need the reverse? Use kVA to Amps.
Calculator
Enter amps, voltage, and phase. Result updates instantly. PF is not required for amps → kVA.
Advanced settings ▾
About this calculator
This amps to kVA calculator converts line current to apparent power. It is the reverse of kVA to Amps. After you have kVA, continue to breaker/cable sizing or browse the power calculator hub.
Calculation Results
≈ 83.14 kVA apparent power
100 A · 480 V · 3-phase · V_L-L
Formula: kVA = √3 × I × V_L-L ÷ 1000
At PF 1.0 (apparent = real — not for motors/UPS with lagging PF):
- 83,138 W · 83.14 kW
- 83,138 VA · 111.44 HP (electrical, ÷0.746)
Need real kW at actual PF? Use Amps to kW.
Balanced RMS estimate. Harmonics, continuous-load margins, and OEM derates are not applied—use results for screening, then verify with engineering judgment.
Continue Your Calculation
Have apparent power from amps? Cross-check line current on kVA to Amps, or continue to breaker sizing.
Amps to kVA conversion charts
Quick-reference tables matching common US/EU voltages. Click an amps button to load the calculator (1φ presets use 240 V; 3φ presets use 480 V).
Single-phase — kVA = I × V ÷ 1000
| Amps | 120 V | 208 V | 220 V | 240 V | 277 V | 480 V |
|---|---|---|---|---|---|---|
| 1.2 | 2.08 | 2.2 | 2.4 | 2.77 | 4.8 | |
| 1.8 | 3.12 | 3.3 | 3.6 | 4.16 | 7.2 | |
| 2.4 | 4.16 | 4.4 | 4.8 | 5.54 | 9.6 | |
| 3.6 | 6.24 | 6.6 | 7.2 | 8.31 | 14.4 | |
| 4.8 | 8.32 | 8.8 | 9.6 | 11.08 | 19.2 | |
| 6 | 10.4 | 11 | 12 | 13.85 | 24 | |
| 7.2 | 12.48 | 13.2 | 14.4 | 16.62 | 28.8 | |
| 9.6 | 16.64 | 17.6 | 19.2 | 22.16 | 38.4 | |
| 12 | 20.8 | 22 | 24 | 27.7 | 48 | |
| 18 | 31.2 | 33 | 36 | 41.55 | 72 | |
| 24 | 41.6 | 44 | 48 | 55.4 | 96 | |
| 48 | 83.2 | 88 | 96 | 110.8 | 192 |
Three-phase (L-L) — kVA = √3 × I × V ÷ 1000
| Amps | 208 V | 220 V | 380 V | 400 V | 415 V | 480 V |
|---|---|---|---|---|---|---|
| 3.6 | 3.81 | 6.58 | 6.93 | 7.19 | 8.31 | |
| 5.4 | 5.72 | 9.87 | 10.39 | 10.78 | 12.47 | |
| 7.21 | 7.62 | 13.16 | 13.86 | 14.38 | 16.63 | |
| 10.81 | 11.43 | 19.75 | 20.78 | 21.56 | 24.94 | |
| 14.41 | 15.24 | 26.33 | 27.71 | 28.75 | 33.26 | |
| 18.01 | 19.05 | 32.91 | 34.64 | 35.94 | 41.57 | |
| 21.62 | 22.86 | 39.49 | 41.57 | 43.13 | 49.88 | |
| 28.82 | 30.48 | 52.65 | 55.43 | 57.5 | 66.51 | |
| 36.03 | 38.11 | 65.82 | 69.28 | 71.88 | 83.14 | |
| 54.04 | 57.16 | 98.73 | 103.92 | 107.82 | 124.71 | |
| 72.05 | 76.21 | 131.64 | 138.56 | 143.76 | 166.28 | |
| 144.11 | 152.42 | 263.27 | 277.13 | 287.52 | 332.55 |
Values in kVA. For line-to-neutral three-phase, open Advanced and select V_L-N (×3 formula).
Amps to kVA formula
Single-phase: kVA = I × V ÷ 1000
Three-phase (line-to-line): kVA = √3 × I × V_L-L ÷ 1000
Three-phase (line-to-neutral): kVA = 3 × I × V_L-N ÷ 1000
- I — balanced RMS line current (amps)
- V — RMS voltage matching the formula basis (L-L or L-N)
- PF not required for kVA — use Amps to kW for real power at actual PF
Excel / Sheets formulas
Put amps in A2 and volts in B2:
- Single-phase:
=(A2*B2)/1000 - Three-phase L-L:
=(SQRT(3)*A2*B2)/1000 - Three-phase L-N:
=(3*A2*B2)/1000
DC note (not this calculator’s default)
For DC, apparent power collapses to kVA = I × V ÷ 1000 (same as single-phase AC). This page defaults to AC 1φ/3φ. Prefer DC-specific tooling when sizing battery buses.
Example 1: 100 A × 480 V × √3 ÷ 1000 = 83.14 kVA (3φ L-L).
Example 2: 60 A × 240 V ÷ 1000 = 14.4 kVA (1φ) → @PF 1.0 ≈ 14.4 kW / 19.3 HP.
Example 3: 200 A × 400 V × √3 ÷ 1000 = 138.56 kVA (3φ L-L)—next screen a breaker on Breaker Size or a set on Generator Size.
Worked 3-phase examples: 3-phase power formula examples. Reverse direction: kVA to Amps.
When to use which tool
| Goal | Tool |
|---|---|
| Convert amps → kVA (this page) | Amps to kVA |
| Convert kVA → line amps | kVA to Amps |
| Convert amps → kW (needs PF) | Amps to kW |
| Generator kVA from load | Generator Size |
| Screen breaker / cable from amps | Breaker Size · Cable Size |
Typical uses: generator kVA from measured feeder amps, transformer apparent-power screening, UPS/inverter kVA from AC current, and distribution planning before breaker/cable selection.
Frequently Asked Questions
How do I convert amps to kVA for a three-phase system?
Use kVA = √3 × I × V ÷ 1000 with line-to-line voltage. Example: 100 A @ 400 V ≈ 69.28 kVA. For L-N voltage, open Advanced and use kVA = 3 × I × V_L-N ÷ 1000.
What is 100 amps to kVA?
At 480 V 3φ ≈ 83.14 kVA. At 400 V 3φ ≈ 69.28 kVA. At 240 V 1φ ≈ 24 kVA. Use the 100 A chart row or presets.
Do I need power factor to convert amps to kVA?
No for kVA. The W / kW / HP figures shown under the result assume PF 1.0 only. For real kW at a known PF, use Amps to kW.
How do I calculate amps to kVA in Excel?
1φ: =(A2*B2)/1000. 3φ L-L: =(SQRT(3)*A2*B2)/1000. 3φ L-N: =(3*A2*B2)/1000 (amps in A2, volts in B2).
How is amps to kVA different from kVA to amps?
This page is amps → kVA. Reverse conversion is on kVA to Amps.
Is amps to kvar the same as amps to kVA?
No. kVAR is reactive power. Use a power-triangle / PF tool when you need kVAR—not this converter.
Related Tools
- kVA to Amps Calculator (Instant, Free, with Formula & Charts)
- Amps to kW Calculator (Instant, Free, with Formula & Examples)
- Circuit Breaker Size Calculator
- Wire Size Calculator (AWG & mm²)
- 3 Phase Power Calculator (Instant, Free) — Electrical Formulas
- kW to kVA Calculator (Instant, Free, with Formula & Examples)
- Generator Size Calculator (kW/kVA)
- Factory Load Calculator