Soft Starter Sizing Calculator
Calculate a minimum current-rating screen from motor FLA and explicit duty/site factors. This is a planning check before the exact manufacturer thermal and application selection.
About this calculator
Quick Calculator inputs above give an instant result; use Advanced fields (factors, units, or decoding) when your datasheet differs from defaults.
Example: 100 A FLA with application factor 1.15 and ambient derate → screen starter rated current before OEM thermal tables.
Result explanation / How to use: treat values as screening only. Engineering assumption and disclaimer: confirm nameplate limits, OEM selectors, and site conditions before procurement or programming.
Hub: Protection calculators — continue related sizing from this topic cluster.
Soft-starter current screen
Current-rating result
Formula and boundary:
What this calculation does
The tool divides explicit application current by the product of entered rating factors. It does not invent universal ambient or altitude derating: manufacturer values differ by series and installation.
Primary references: ABB Softstarter Catalog and Schneider Electric Altistart selection guidance.
Frequently Asked Questions
Which current starts the calculation?
Use motor nameplate FLA, not breaker size or locked-rotor current.
Can I use a 1.0 application factor?
Only when the current OEM selector and application classification support it.
Does current limit predict acceleration?
No. Load torque and inertia determine whether the motor accelerates at that limit.
What must I verify next?
Verify thermal start duty, starts per hour, bypass, coordination and installation derating with the manufacturer.