EV Charger Load Calculator
Screen Level 2 EVSE continuous amps and a 125% breaker frame—instant load planning for home charger circuits.
Calculator
Quick: continuous amps × 1.25 → breaker. Advanced: enter kW at voltage instead of amps.
About this calculator
Screens EV charger / EVSE continuous load and a breaker frame with a 125% continuous factor. It is not a full NEC 220 dwelling load calculation or OEM installer app. For home Level 2 buying context, open the EV charger for home sizing guide. Continue with cable sizing and the general breaker size calculator on the protection calculators hub.
Calculation Results
Min breaker screen: 40 A
32 A continuous × 1.25 = 40 A → next frame 40 A. This is a planning screen, not a conductor selection or installation approval.
Assumptions: single-phase branch; continuous EVSE; no load management / power sharing modeled. Panel spare capacity must still pass a dwelling load calc.
Continue Your Calculation
Size the EVSE feeder conductor for the screened breaker duty, then check route length in Voltage Drop.
Planning disclaimer
Educational screen only—not a substitute for NEC Article 625 / 220 design, manufacturer instructions, or AHJ approval. Hire a licensed electrician. Confirm GFCI/AFCI and disconnect requirements for your jurisdiction.
EV charger breaker size chart (125% screen)
Common Level 2 continuous settings with a 125% arithmetic screen. Open a row to load the calculator. Conductor size is intentionally not inferred from breaker rating alone. Home buying context: EV charger for home sizing.
| Continuous A | × 1.25 | Breaker screen | ≈ kW @ 240 V | Conductor next step |
|---|---|---|---|---|
| 20 | 20 A | 3.8 kW | Verify ampacity and voltage drop | |
| 40 | 40 A | 7.7 kW | Verify ampacity and voltage drop | |
| 50 | 50 A | 9.6 kW | Verify ampacity and voltage drop | |
| 60 | 60 A | 11.5 kW | Verify ampacity and voltage drop |
Formula & explanation
Breakermin ≥ Icontinuous × 1.25 (typical continuous EVSE screen)
From kW (1φ): Icontinuous = (kW × 1000) ÷ V
80% rule? Running a breaker at ≤80% continuous is the flip side of sizing OCPD at 125% of continuous load—same math, different wording.
Example: 48 A continuous @ 240 V → 48 × 1.25 = 60 A breaker screen · ≈ 11.5 kW.
Chain: this page → cable size → voltage drop · general OCPD ladder: breaker size. Hub: protection calculators.
When to use which protection tool
| Goal | Tool |
|---|---|
| EVSE continuous A → breaker frame | This page |
| General feeder / motor OCPD ladder | Breaker Size Calculator |
| AWG / mm² ampacity | Cable Size Calculator |
| Long garage run voltage drop | Voltage Drop Calculator |
Frequently Asked Questions
What size breaker do I need for an EV charger?
Breaker ≥ continuous A × 1.25, then next standard frame. Example: 32 A → 40 A; 48 A → 60 A.
Why multiply by 1.25?
EVSE is typically a continuous load. The 125% screen keeps the OCPD from running at 100% continuous—often called the “80% rule” from the other direction.
Is a 40 A breaker OK for a 32 A charger?
Yes as a screen: 32 × 1.25 = 40. Still size the wire in Cable Size.
What size wire for a 60 amp EV charger?
The breaker rating alone is insufficient. Verify conductor material and insulation, terminal temperature ratings, wiring method, ambient and bundling adjustments, voltage drop, applicable code and OEM instructions in Cable Size and Voltage Drop. See also EV charger for home.
50 A vs 60 A for Level 2 / Tesla-class?
Match continuous amp setting: 40 A continuous → 50 A breaker; 48 A continuous → 60 A breaker.
Related Tools
- Cable Sizing Chart & Wire Size Calculator
- Circuit Breaker Size Calculator
- Voltage Drop Formula & Calculator (1φ/3φ/DC, Instant)
- kVA to Amps Calculator (Instant, Free) — Also Amps to kVA
- Available Fault Current Calculator
- Motor FLA Calculator (Full Load Amps by HP, kW & Voltage)
- Motor Cable Size Calculator (NEC 430.22 & Voltage Drop)
- VFD Sizing Calculator (Motor HP, Application & Derating)
