3-Phase Power Calculator

Compute balanced three-phase kW and kVA from line V, line A, and PF using the √3 relationship—use Quick Examples for glove-friendly presets (for example a 50 HP fan upgraded from 40 HP: match nameplate FLA, not the old breaker label). Advanced motor inrush, harmonics, and unbalance still need field measurements and coordination studies.

Input Parameters

Quick Examples:

380–415 V IEC-style systems; 480 V is common for North American industrial motor buses (HP-rated loads). Prefer measured line-to-line at the starter.
Typical: Small motor 5-20A, Medium motor 20-100A, Large motor 100-500+ A
Typical: Motors 0.80-0.90, Heaters 1.0, Mixed loads 0.85-0.95

About this calculator

Converts balanced three-phase voltage, line current, and PF into real and apparent power for motor lines and feeders before you lock harmonics or starting multiples. For the rest of the kW/kVA/current chain, use the power calculators hub.

If you start from kW or kVA without line current, use kW to kVA first, then kVA to amps for balanced line A; use factory load when sizing from device counts. After you have design amps, screen cable size (ampacity + installation derating on your tables) and voltage drop on long feeders; breaker size ties to continuous vs non-continuous duty per NEC or IEC 60364 practices.

Calculation Results

Balanced three-phase, steady-state line current; does not replace motor inrush, harmonic, or unbalance studies.

Then screen cable size for tabulated ampacity after installation derating, voltage drop on long runs, and breaker size against continuous duty rules. kVA to amps (3-phase) is the same √3 path when you already know kVA and line-to-line voltage.

Engineering disclaimer

This calculator provides preliminary power calculations only. The motor FLA / breaker table below is illustrative—always use manufacturer nameplate FLA/LRA and IEC 60034 / NEC 430 family rules for thermal and short-circuit protection, selective coordination, and fault levels. For final electrical system design, equipment sizing, and compliance with local electrical codes, consult a licensed electrical engineer or certified professional. Actual requirements may vary based on detailed load analysis, harmonics, motor starting currents, and specific application requirements.

Balanced 3φ power — quick √3 reference

Illustrative kW at PF 0.85 from kW = √3 × VL-L × I × PF ÷ 1000 (line quantities). Use the calculator above for your exact V, I, and PF.

VL-L Line I (A) Approx. kW @ PF 0.85
400105.9
4005029.4
48010070.7

3-Phase Power Formula & Explanation

VL-L
Line-to-line voltage in volts (measured at the equipment or bus).
I (or IL)
Balanced line current in amperes (RMS), one conductor of the three-phase set.
PF (cos φ)
Displacement power factor: ratio of real power to apparent power for fundamental frequency; harmonics need separate treatment.
kW / kVA
Real and apparent power; kVAR (reactive) fills the triangle when PF < 1.

Balanced line quantities: kW = √3 × VL-L × I × PF ÷ 1000 and kVA = √3 × VL-L × I ÷ 1000 so kW = kVA × PF. Example: 400 V, 10 A, PF 0.85 → about 5.9 kW and 6.9 kVA. The green next-step card points to kVA to amps at your voltage and phase.

kW vs kVA vs kVAR: kW is real power; kVA is apparent; kVAR is reactive. Conductors and sources must carry kVA; utility and PFC discussions often focus on kVAR when PF lags.

Motor note: running FLA follows the formulas above; locked-rotor, thermal overloads, and branch protection follow NEC 430 and IEC 60034 / IEC 60364 practices (or your local code)—size devices with those rules, not this steady-state line alone. Fault current and selective coordination are outside this page.

  • Ampacity: tabulated conductor current must be derated for installation method, ambient, grouping, and harmonics on project tables.
  • Balanced load assumed; unbalance needs per-phase work.
  • √3 ≈ 1.732 ties line values to total three-phase power.

More: 3-phase power formula & examples · 3-phase power guide · Factory load · kW to kVA · kVA to amps · Cable size · Voltage drop · Power Calculators Hub

Power triangle
Right triangle: kW along the horizontal leg, kVAR along the vertical leg, kVA as the hypotenuse (apparent power). φ kW (real) kVAR kVA (apparent)

kVA² = kW² + kVAR²; with PF known, PF = kW ÷ kVA.

Motor FLA / breaker quick reference (400 V class)

Illustrative running FLA and order-of-magnitude LRA from nameplate practice; verify NEC 430.52 / 430.22, IEC 60034 nameplate currents, and nameplate LRA before selecting devices.

Motor size Typical FLA (400V) Typical LRA Screening breaker (inverse-time)
5 HP7–8 A42–56 A20 A class
10 HP14–16 A84–112 A30 A class
25 HP35–40 A210–280 A60 A class
50 HP70–75 A420–560 A200 A class
100 HP140–150 A840–1200 A400 A class

From HP use 1 HP ≈ 0.746 kW, then FLA ≈ kW × 1000 ÷ (√3 × V × PF × η) with nameplate η when known. This table is not a substitute for OEM data, cable ampacity, or fault studies.

Frequently Asked Questions

What is the difference between line current and phase current in three-phase systems?

Line current flows in each supply conductor; phase current flows in each winding. In delta, line current equals phase current times √3; in wye (star), line current equals phase current. Field work usually starts from line quantities.

How do I calculate kVA from kW in a three-phase system?

kVA = kW ÷ power factor. Example: 10 kW at PF 0.85 gives about 11.76 kVA. The calculator shows both once V, I, and PF are set.

What power factor should I use for different types of loads?

Resistive loads are near PF 1.0; motors often 0.8–0.9; electronics often 0.9–0.95. For mixed plants use a weighted average or the lowest PF for a conservative envelope; 0.85 is a common placeholder when data is thin.

Why is the recommended breaker rating higher than the calculated current?

Protective devices are sized above steady-state FLA for continuous-duty margins (often 125% where codes require), inrush, coordination, and future load growth—always follow NEC, IEC 60364 family rules, or your local code and manufacturer tables.

Can I use this calculator for single-phase systems?

No. This page assumes balanced three-phase with √3 in the power equation. Single-phase real power uses P = V × I × PF without √3; use a single-phase calculator for those branches.

How do I calculate 3-phase current from kilowatts?

I (A) = (kW × 1000) ÷ (√3 × V_L-L × PF). Example: 10 kW at 400 V and PF 0.85 is about 17 A. Always use measured V and PF when commissioning.

What is the difference between kW and kVA in 3-phase systems?

kW is real power; kVA is apparent power. kW = kVA × PF. Size transformers and generators on kVA; utility demand charges often track both kW and PF.

How do I convert horsepower to kilowatts for 3-phase motors?

1 HP ≈ 0.746 kW. Convert HP to kW, then use the three-phase current formula with nameplate PF and efficiency when known; remember locked-rotor and starting multiples are not modeled here.

What voltage should I use for 3-phase calculations?

Use line-to-line (phase-to-phase) voltage. Nominal 380/400/415 V is common in IEC markets; 480 V is common in North America. Prefer measured bus voltage at the equipment terminals when harmonics or long feeders skew the nameplate assumption.

How do I calculate 3-phase power factor from current and voltage?

If kW and kVA are known, PF = kW ÷ kVA. If kW, line-to-line voltage, and line current are known, PF = (kW × 1000) ÷ (√3 × V × I). Example: 10 kW at 400 V with 20 A line current is about 0.72 PF. Very low PF may trigger correction or utility penalties.

Why is my 3-phase current calculation different from measured values?

Mismatch comes from nominal versus measured voltage, true PF versus assumed PF, phase unbalance, harmonics, VFD waveforms, and instrument accuracy. Use clamp-on RMS readings at the load and reconcile with the site energy meter when disputes arise.