Ground Wire Size Calculator
Size the equipment grounding conductor from the breaker (NEC Table 250.122) or the grounding electrode conductor from the service conductors (Table 250.66). For AC NEC work only — not 12 V DC earthing, and not phase-wire ampacity.
Ground wire inputs
Optional NEC 250.122(B): if ungrounded conductors were increased for voltage drop, enlarge the EGC in the same circular-mil ratio.
About this calculator
EGC size follows the overcurrent device. GEC size follows the service conductors, then may be capped by electrode type. Continue on the protection calculators hub after you size phase conductors.
Result
Planning estimate. Confirm the published NEC edition and local amendments before you pull wire.
Continue Your Calculation
Next, size the ungrounded (phase) conductors for ampacity and length. Ground-wire size does not replace cable ampacity.
NEC ground wire quick tables
Same screening values as the calculator. EGC uses Table 250.122 (OCPD not exceeding). GEC uses Table 250.66 (largest ungrounded service conductor).
| OCPD not exceeding | EGC copper | EGC aluminum |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 300 A | 4 AWG | 2 AWG |
| 400 A | 3 AWG | 1 AWG |
| 600 A | 1 AWG | 2/0 AWG |
| 800 A | 1/0 AWG | 3/0 AWG |
| 1200 A | 3/0 AWG | 250 kcmil |
| Largest Cu service conductor | GEC copper | GEC aluminum |
|---|---|---|
| 2 AWG or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 AWG | 6 AWG | 4 AWG |
| 2/0 or 3/0 AWG | 4 AWG | 2 AWG |
| Over 3/0 through 350 kcmil | 2 AWG | 1/0 AWG |
| Over 350 through 600 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | 3/0 AWG | 250 kcmil |
Rod/pipe/plate only: GEC not required larger than 6 AWG copper or 4 AWG aluminum (250.66(A)). Concrete-encased only: not required larger than 4 AWG copper (250.66(B)).
Formula & method
EGC: look up the overcurrent device in Table 250.122. If ungrounded conductors were increased for voltage drop, EGC_cmil = Table_EGC_cmil × (actual_phase_cmil ÷ minimum_phase_cmil), then round up to the next standard size (250.122(B)).
GEC: look up the largest ungrounded service-entrance conductor in Table 250.66, then apply electrode caps 250.66(A)/(B)/(C) when the conductor connects only to that electrode type.
Example: 200 A breaker → EGC 6 AWG copper. Same 200 A service with 2/0 copper feeders → GEC table size 4 AWG copper; to rods only → may stop at 6 AWG copper under 250.66(A).
200 amp ground wire worked example
| Question | Answer on this page |
|---|---|
| EGC with a 200 A feeder / breaker | 6 AWG copper or 4 AWG aluminum (250.122) |
| GEC from 2/0 Cu or 4/0 Al service (full table) | 4 AWG copper or 2 AWG aluminum (250.66) |
| Same GEC to ground rods only | Not required larger than 6 AWG copper / 4 AWG aluminum (250.66(A)) |
Phase conductors for a 200 A dwelling service are a different task — use the cable size calculator (and the future 200 A service table on that page).
FAQ
What size ground wire is required for a 60-amp circuit?
For an equipment grounding conductor on a 60 A overcurrent device, NEC Table 250.122 requires 10 AWG copper or 8 AWG aluminum.
What size ground wire for a 200 amp service?
It depends which ground wire you mean. The EGC with a 200 A feeder is typically 6 AWG copper (Table 250.122). The GEC from a typical 2/0 copper or 4/0 aluminum 200 A service is 4 AWG copper by Table 250.66, but if that conductor connects only to ground rods, 250.66(A) does not require larger than 6 AWG copper.
What is the difference between an EGC and a GEC?
An equipment grounding conductor (EGC) runs with the circuit conductors and is sized from the breaker by Table 250.122. A grounding electrode conductor (GEC) bonds the service or separately derived system to earth electrodes and is sized from the service conductors by Table 250.66.
Does a ground rod always need 4 AWG copper?
No. NEC 250.66(A) says a GEC that connects only to rod, pipe, or plate electrodes is never required to be larger than 6 AWG copper or 4 AWG aluminum. Some local rules still require 4 AWG copper; that is an AHJ amendment, not the national rod cap.
Does this calculator size phase conductors?
No. Phase and neutral ampacity stay on the cable size calculator. This page only sizes EGC and GEC ground wires.
Related Tools
- Cable Sizing Chart & Wire Size Calculator
- Circuit Breaker Size Calculator
- Voltage Drop Formula & Calculator (1φ/3φ/DC, Instant)
- Conduit Fill Calculator
- Available Fault Current Calculator
- Motor FLA Calculator (Full Load Amps by HP, kW & Voltage)
- Motor Cable Size Calculator (NEC 430.22 & Voltage Drop)
- VFD Sizing Calculator (Motor HP, Application & Derating)