Ground Wire Size Calculator

Size the equipment grounding conductor from the breaker (NEC Table 250.122) or the grounding electrode conductor from the service conductors (Table 250.66). For AC NEC work only — not 12 V DC earthing, and not phase-wire ampacity.

Ground wire inputs

Amperes of the OCPD ahead of the circuit (example: 200)

About this calculator

EGC size follows the overcurrent device. GEC size follows the service conductors, then may be capped by electrode type. Continue on the protection calculators hub after you size phase conductors.

Result

Planning estimate. Confirm the published NEC edition and local amendments before you pull wire.

Assumptions: wire-type EGC or GEC. Raceway used as the EGC is not sized here. Parallel service equivalent area is not auto-summed. This screen does not size phase conductors.

Continue Your Calculation

Next, size the ungrounded (phase) conductors for ampacity and length. Ground-wire size does not replace cable ampacity.

NEC ground wire quick tables

Same screening values as the calculator. EGC uses Table 250.122 (OCPD not exceeding). GEC uses Table 250.66 (largest ungrounded service conductor).

OCPD not exceedingEGC copperEGC aluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1200 A3/0 AWG250 kcmil
Largest Cu service conductorGEC copperGEC aluminum
2 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4 AWG2 AWG
Over 3/0 through 350 kcmil2 AWG1/0 AWG
Over 350 through 600 kcmil1/0 AWG3/0 AWG
Over 600 through 1100 kcmil2/0 AWG4/0 AWG
Over 1100 kcmil3/0 AWG250 kcmil

Rod/pipe/plate only: GEC not required larger than 6 AWG copper or 4 AWG aluminum (250.66(A)). Concrete-encased only: not required larger than 4 AWG copper (250.66(B)).

Formula & method

EGC: look up the overcurrent device in Table 250.122. If ungrounded conductors were increased for voltage drop, EGC_cmil = Table_EGC_cmil × (actual_phase_cmil ÷ minimum_phase_cmil), then round up to the next standard size (250.122(B)).

GEC: look up the largest ungrounded service-entrance conductor in Table 250.66, then apply electrode caps 250.66(A)/(B)/(C) when the conductor connects only to that electrode type.

Example: 200 A breaker → EGC 6 AWG copper. Same 200 A service with 2/0 copper feeders → GEC table size 4 AWG copper; to rods only → may stop at 6 AWG copper under 250.66(A).

200 amp ground wire worked example

QuestionAnswer on this page
EGC with a 200 A feeder / breaker6 AWG copper or 4 AWG aluminum (250.122)
GEC from 2/0 Cu or 4/0 Al service (full table)4 AWG copper or 2 AWG aluminum (250.66)
Same GEC to ground rods onlyNot required larger than 6 AWG copper / 4 AWG aluminum (250.66(A))

Phase conductors for a 200 A dwelling service are a different task — use the cable size calculator (and the future 200 A service table on that page).

FAQ

What size ground wire is required for a 60-amp circuit?

For an equipment grounding conductor on a 60 A overcurrent device, NEC Table 250.122 requires 10 AWG copper or 8 AWG aluminum.

What size ground wire for a 200 amp service?

It depends which ground wire you mean. The EGC with a 200 A feeder is typically 6 AWG copper (Table 250.122). The GEC from a typical 2/0 copper or 4/0 aluminum 200 A service is 4 AWG copper by Table 250.66, but if that conductor connects only to ground rods, 250.66(A) does not require larger than 6 AWG copper.

What is the difference between an EGC and a GEC?

An equipment grounding conductor (EGC) runs with the circuit conductors and is sized from the breaker by Table 250.122. A grounding electrode conductor (GEC) bonds the service or separately derived system to earth electrodes and is sized from the service conductors by Table 250.66.

Does a ground rod always need 4 AWG copper?

No. NEC 250.66(A) says a GEC that connects only to rod, pipe, or plate electrodes is never required to be larger than 6 AWG copper or 4 AWG aluminum. Some local rules still require 4 AWG copper; that is an AHJ amendment, not the national rod cap.

Does this calculator size phase conductors?

No. Phase and neutral ampacity stay on the cable size calculator. This page only sizes EGC and GEC ground wires.