Voltage Drop Formula & Calculator

Free voltage drop calculator with the instant voltage drop formula for DC / 1φ / —then screen NEC AWG or IEC mm² on the same page.

  • DC / 1φ: VD = 2 × I × L × R (NEC: (2 × K × I × L) ÷ CM)
  • 3φ voltage drop formula: VD = √3 × I × L × R (NEC: (√3 × K × I × L) ÷ CM)
  • %: (VD ÷ Vnom) × 100 — often ≤3% branch / ≤5% feeder+branch

Need R·X / NEC 3%/5% worked proofs? voltage drop calculation guide. After % is OK → cable size · breaker size.

Quick presets (IEC / mm²)

Load metric examples, then refine.

Calculator inputs

Code / units mode
Steady-state line current used for the voltage drop check.
NEC K-method uses one-way feet; the 2 or √3 factor accounts for the circuit.

Advanced calculator settings

Set conductor material, circuit type, and the nominal voltage that matches the same design basis. These settings refine a resistive screening result; they do not replace impedance, thermal, or installation-method studies.

Use L-N for typical 1φ / DC descriptions or L-L for 3φ (e.g. 480 V). Stay consistent with your design basis.

About this calculator

This free voltage drop calculator is the live landing for voltage drop calculator and 3 phase voltage drop calculation formula screens—steady-state resistive drop for copper or aluminum runs with NEC AWG / K-method or IEC mm². Pick ampacity first on cable size, then verify % here. Method depth: 3-phase voltage drop formula guide. Hub: protection calculators.

Parallel conductors & temperature (Southwire-style notes): If you run N parallel conductors per phase, divide the per-conductor current by N before reading % drop (or multiply ampacity capacity). Ambient above 30 °C and steel conduit AC reactance are not modeled here—use OEM/Southwire tables for final compliance. This page remains a resistive screening tool.

Results

Results (NEC / AWG)

Voltage drop: ~7.9 V (example: 20 A · 100 ft · 12 AWG Cu · 120 V)
Drop (%): ~6.6% — compare to your 3% / 5% planning limit.
Model: NEC K-method screening (K=12.9 Cu). Switch modes or edit inputs for live results.
NEC planning check (5%): Above the selected planning limit — upsize AWG or shorten the run.

Apply suggested ~10 AWG on cable / wire gauge →

Live results update when you change inputs above. Formula: DC / 1φ / 3φ voltage drop formula.

Engineering disclaimer

Reactance, power factor, parallel runs, conduit temperature, and harmonic currents are not modeled. This is not a substitute for NEC Chapter 9 / IEC 60364-5-52 tables or engineer-stamped calculations.

Voltage drop % quick-reference table (NEC Cu, K-method)

Screening look-up for copper, single-phase / DC (2×K·I·L÷CM). Values are approximate percent of nominal voltage. Low-voltage DC (12 V) shows much higher % for the same AWG and feet—use the 12 V DC presets above to verify.

AWG 20 A · 100 ft · 120 V 40 A · 100 ft · 240 V 20 A · 200 ft · 120 V 20 A · 25 ft · 12 V DC
14 AWG10.5%10.5%20.9%26.2%
12 AWG6.6%6.6%13.2%16.5%
10 AWG4.1%4.1%8.3%10.4%
8 AWG2.6%2.6%5.2%6.5%
6 AWG1.6%1.6%3.3%4.1%

Note: 40 A · 100 ft · 240 V matches 20 A · 100 ft · 120 V % for the same AWG because both Vd and Vnom scale together in this resistive screen. Planning screens often target ≤3% branch / ≤5% feeder+branch. Confirm ampacity on the wire gauge / cable size calculator.

Voltage drop formula (NEC AWG & IEC)

3 phase voltage drop calculation formula

Live screen on this page: VD = (√3 × K × I × L) ÷ CM (NEC) or VD = √3 × I × L × R (IEC resistivity). Worked: 100 A · 200 ft · 3 AWG Cu → ≈ 8.5 V ≈ 1.8% @ 480 V — use preset 100 A · 200 ft · 3 AWG · 480 V 3φ. Full R·X derivation: guide Quick answer.

NEC / AWG (K-method)

Single-phase / DC: VD = (2 × K × I × L) ÷ CM

Three-phase: VD = (√3 × K × I × L) ÷ CM

K ≈ 12.9 (Cu) or 21.2 (Al); I = amps; L = one-way feet; CM = circular mils (NEC Chapter 9 Table 8 style). Percent = (VD ÷ Vnom) × 100. Planning discussions often cite ≤3% branch and ≤5% combined feeder+branch (informational notes).

AWG → circular mils (CM) screening values
AWG CM AWG CM
144110441740
126530266360
10103801/0105600
8165102/0133100
6262404/0211600

DC voltage drop (explicit)

Choose DC (2-wire) in the calculator. NEC mode uses the same 2 × K × I × L ÷ CM screen as single-phase AC; IEC mode uses 2×R. For 12 V DC voltage drop / battery runs, percent loss rises quickly—use the 12 V presets, then confirm ampacity on the wire gauge calculator.

IEC / mm² (resistive)

Resistance one way: R = ρ · L / A. Copper ρ ≈ 0.017241; aluminum ≈ 0.028265 (Ω·mm²/m at 20 °C).

Single-phase / DC: V ≈ I · 2R. Three-phase: V ≈ √3 · I · R.

Deep dive: NEC 3%/5% voltage drop limits & worked examples.

Worked examples

NEC AC: 20 A, 100 ft one-way, 12 AWG Cu (6530 CM), 120 V 1φ → VD = (2 × 12.9 × 20 × 100) / 6530 ≈ 7.9 V6.6%. Use the 120 V preset above.

12 V DC voltage drop: 20 A, 25 ft, 10 AWG Cu → ≈ 1.24 V10.4% of 12 V (often too high for battery/inverter loads). Same run on 6 AWG → ≈ 4.1%. Use the 12 V DC presets.

Long feeder: 20 A, 250 ft, 10 AWG @ 120 V → ≈ 10.4%—upsize AWG or shorten the route. Use the long-run preset.

IEC: 16 A, 25 m, 2.5 mm² Cu, 230 V 1φ → ≈ 5.5 V / 2.4%. Use the metric presets.

Guides

Frequently asked questions

What is the NEC voltage drop formula (AWG)?

Screening form: 1φ/DC VD = (2 × K × I × L) ÷ CM; 3φ VD = (√3 × K × I × L) ÷ CM. K ≈ 12.9 Cu / 21.2 Al; L is one-way feet; CM from wire gauge. Select NEC / AWG mode above. These are planning checks—not a substitute for Chapter 9 impedance designs.

What is the 3 phase voltage drop calculation formula?

3 phase voltage drop calculation formula (resistive screen): VD = √3 × I × L × R, or NEC AWG VD = (√3 × K × I × L) ÷ CM. Example: 100 A · 200 ft · 3 AWG Cu · K 12.9 → ≈ 8.5 V; at 480 V ≈ 1.8%. Enter the same load above—full R·X form and NEC 3%/5% proofs: voltage drop calculation guide. Then confirm ampacity on cable size.

What is the voltage drop formula for 3 phase?

Voltage drop formula 3 phase (K-method): VD = (√3 × K × I × L) ÷ CM with one-way feet. With reactance: VD = √3 × I × (R cos θ + X sin θ) × L. Set System = 3-phase in this voltage drop calculator for an instant % screen.

Is this a voltage drop calculator?

Yes. Enter current, one-way length, and AWG or mm² for volts and percent on 1φ / 3φ / DC feeders. After % looks acceptable, size/confirm the conductor on the cable size calculator.

What are the NEC 3% and 5% voltage drop limits?

Informational notes discuss about 3% for branch (or feeder) and 5% combined feeder+branch. They are recommendations, not always enforceable rules—confirm with your AHJ. Use the planning-limit control in NEC mode.

How do you calculate voltage drop in a cable?

Use NEC AWG K-method (feet + circular mils) or IEC mm² resistivity (ρ·L/A). Select NEC or IEC mode above for 1φ, 3φ, or DC resistive screening—then confirm ampacity on the wire / cable size calculator.

What is the voltage drop per 100 ft?

It depends on amps, AWG, Cu/Al, phase, and voltage. Example screen: 20 A · 100 ft · 12 AWG Cu · 120 V 1φ ≈ 7.9 V ≈ 6.6%. Use the % quick-reference table or enter 100 ft in NEC mode for your exact load.

What is a volt drop calc vs voltage drop calculator?

Volt drop calc is the same screening job as a voltage drop calculator. Enter current, length, and conductor size (AWG or mm²) for volts and percent—then confirm ampacity on the cable size & wire gauge calculator.

Can I use this for DC voltage drop or DC voltage loss?

Yes. Choose DC (2-wire) in System. NEC mode uses the 2×K formula; IEC mode uses 2×R. It estimates ohmic loss, not converter or battery internal impedance. For 12 V battery / inverter runs, try the 12 V DC presets—percent drop is much higher than on 120 V for the same AWG and length.

Where is a voltage drop calculation table?

Use the % drop quick-reference table above for 20 A copper screening by AWG and length (including a 12 V DC column). For your exact current and gauge, enter values in the calculator—the table is a planning look-up, not a full Chapter 9 reprint.

Is this a voltage drop across a resistor calculator?

No. This page is for cable / feeder voltage drop in electrical distribution. Electronics V = IR across a discrete resistor is a different problem.

Why is my percent drop different from NEC examples?

Full NEC examples often include AC resistance/reactance, power factor, and temperature. This page’s NEC mode is a K-method resistive screen; IEC mode uses 20 °C DC resistivity. Use code tables for binding designs.

Should I use line-to-line or line-to-neutral voltage for %?

Use the same reference your team uses for the circuit being studied. Be explicit in reports; mixing references changes the percentage even if the physical drop in volts is unchanged.

What if I need a smaller drop?

Increase conductor size (next AWG/mm²), shorten the route, reduce current, or raise system voltage. Confirm ampacity and protection independently on the wire gauge / cable size tool.

Does aluminum behave the same way in the tool?

Same formulas with higher K (21.2) or resistivity. Terminations, oxidation control, and ampacity tables still require manufacturer and code guidance.

Related tools and hub

Use this result with: Cable Size Calculator, Breaker Size Calculator, and kVA to Amps Calculator.

Protection calculators hub