3-Phase Cable Size Calculator (mm² & AWG, IEC and NEC)

Size wire/cable from amps or kW (1φ / 3φ / DC)—AWG + mm². Then check voltage drop. 3φ: 10 kW · 400 V · PF 0.85 → ~17 A → 2.5–4 mm².

Calculator

Amps or kW + PF → AWG + mm² for 1φ / 3φ / DC.

Load input

Common wire sizing

Industrial & DC scenarios

The AWG column used is the lower of this termination rating and the insulation rating. 75°C only when the equipment marking allows it.

This page has 60°C and 75°C NEC ladders. A 90°C insulation rating is capped at the 75°C ladder, then limited again by the termination rating.

Advanced — derating & run length

Enter correction factors from the adopted wiring code and the actual conductor insulation, ambient, installation and grouping conditions. The calculator does not choose these factors.

Used only when a rooftop distance is selected. 30°C is the table base.
Screening adders from the former NEC 2017 Table 310.15(B)(3)(c). Later NEC editions removed this table. Confirm the adopted code before use.
Run length unit
With a length + VD % limit below, this page upsizes AWG/mm² when the resistive screen exceeds the target (Southwire-style ampacity + drop). Blank length = ampacity only.
Matches competitor “wire size + voltage drop” screens. Planning notes only—confirm with AHJ / Chapter 9.
1.00 keeps the resistive screen. Below 1.00 adds screening reactance. Not used for DC.
0.051 ohm/1000 ft nonmagnetic, 0.068 ohm/1000 ft steel. Not a full Chapter 9 Table 9.

Open full voltage drop calculator →

Tip: Switch to From kW for a one-step 3-phase cable size from load power, or keep amps for direct screening.

About this calculator

This free wire size calculator turns design amps or kW + PF into an NEC-style AWG screen plus the next standard mm² for single-phase AC, three-phase AC, and DC—optionally apply illustrative Ca/Cg derating—before you lock BOMs or panel schedules. Hub: protection calculators. After sizing, verify long runs on the NEC / AWG voltage drop calculator. Guides: voltage drop calculation, Motor Starting Current & Protection.

Prefer From kW for a one-step 3-phase cable size (Ib = P ÷ (√3 × V × PF)), or keep From design amps when you already have line current from 3-phase power / kVA to amps. For 12 V DC, use the battery preset and DC / 12V notes.

Calculation Results

Calculation Results

Design Current (Ib): 63 A
System: Three Phase, 400 V, Copper conductor
Wire gauge screen (NEC 2023 Table 310.16, 60°C column): 4 AWG for ≈63 A Cu before installation corrections
Cable size screen (IEC mm² ladder): 16 mm²

Enter one-way run length under Advanced to prefill the NEC voltage drop or IEC voltage drop calculator.

IEC mm² ladder plus NEC 2023 Table 310.16 AWG screen for planning only. Optional Advanced Ca/Cg factors inflate screening current; this page does not apply small-conductor OCPD limits, parallel-conductor rules, terminal-temperature exceptions beyond the selected column, or short-circuit withstand.

Engineering disclaimer

This calculator provides cable screening estimates only. For final electrical system design, conductor selection, and compliance with local electrical codes, consult a licensed electrical engineer or certified professional. Actual requirements may vary based on installation method, ambient conditions, harmonics, and specific application requirements.

Wire ampacity chart — AWG cable size chart (gauge → mm², circular mils, Cu & Al ampacity)

Lookup-style wire ampacity chart / AWG cable size chart / copper cable size chart for American Wire Gauge (gauge cable size = AWG). Read diameter-equivalent mm², circular mils, and illustrative ampacity of wire for copper and aluminum conductors (NEC 2023 Table 310.16-style columns at 60/75/90 °C, 30 °C ambient, ≤3 current-carrying conductors). Stranded cable uses the same AWG area; overall OD can be larger than solid. Confirm insulation temperature, terminals, and derating on your project tables—not a code reprint.

AWG Area (mm²) Circular mils Cu ampacity 60 °C Cu ampacity 75 °CCu ampacity 90 °CAl ampacity 60 °CAl ampacity 75 °CAl ampacity 90 °C
14 AWG2.084,11015 A*20 A*25 A*———
12 AWG3.316,53020 A*25 A*30 A*15 A*20 A*25 A*
10 AWG5.2610,38030 A*35 A*40 A*25 A*30 A*35 A*
8 AWG8.3716,51040 A50 A55 A35 A40 A45 A
6 AWG13.326,24055 A65 A75 A40 A50 A55 A
4 AWG21.241,74070 A85 A95 A55 A65 A75 A
3 AWG26.752,62085 A100 A110 A65 A75 A85 A
2 AWG33.666,36095 A115 A130 A75 A90 A100 A
1 AWG42.483,690110 A130 A145 A85 A100 A115 A
1/0 AWG53.5105,600125 A150 A170 A100 A120 A135 A
2/0 AWG67.4133,100145 A175 A195 A115 A135 A150 A
3/0 AWG85.0167,800165 A200 A220 A130 A155 A175 A
4/0 AWG107.2211,600195 A230 A260 A150 A180 A205 A

*14 / 12 / 10 AWG small conductors (Cu & Al) also limited by NEC 240.4(D) small-conductor OCPD rules in many branch circuits. Ampacity columns are an NEC Table 310.16-adjacent reference (0–2000 V insulated conductors, ≤3 current-carrying conductors, 30 °C ambient) — not a code reprint. Need amps → size instead? Use the cable size chart or the calculator above. Metric column = IEC-style mm² cross-check for the same AWG area.

Wire and Cable Size Chart (AWG & mm² by Current)

Field-style wire size chart / cable size chart / copper cable size chart (amps → next mm²) from the same IEC 60228-style ladder used in the calculator. For gauge-first lookup see the AWG cable size chart. Click a current to load the calculator; verify tabulated ampacity after derating and voltage drop. AWG is an approximate NEC cross-check only—not conduit trade size.

120V wire size: For a 120 V branch, select single-phase AC and enter the design current (or click 120 V branch · 20 A · 100 ft). If you know the one-way run length, use Advanced to review estimated voltage-drop impact. The suitable conductor depends on the adopted code, insulation and terminal ratings, installation method, and OCPD rules—this chart is a screening aid, not a universal ampacity stamp for every 120 V job.

Design current (A) Next standard Cu mm² (screening) Approx. AWG (NEC ref.)
1.516 AWG
2.514 AWG
412 AWG
610 AWG
108 AWG
166 AWG
254 AWG (IEC) / ~3 AWG @75°C NEC
352 AWG
501 AWG
702/0 AWG

Conduit sizing for wire? This page sizes conductor ampacity, not raceway trade size. After you pick AWG/mm², use NEC Chapter 9 Annex C (or manufacturer fill tables) for conduit/EMT fill %. In conduit, still apply ambient + grouping derating (Advanced Ca/Cg) before locking the BOM.

Battery cable size chart (12 V DC · amps × length → AWG)

Screening battery cable size chart for battery cable size on 12 V copper runs: target ≤3% drop (0.36 V) using a 2-wire resistive screen (same idea as Advanced length on this calculator). Lengths are one-way feet—enter the same one-way length in the tool. Also meet ampacity from the AWG copper ampacity columns. Click 12 V battery · 50 A · 15 ft above, then verify on the NEC / DC voltage drop calculator.

Amps 5 ft OW 10 ft 15 ft 20 ft 25 ft
30 A8 AWG6 AWG4 AWG3 AWG2 AWG
50 A8 AWG4 AWG2 AWG1 AWG1/0 AWG
75 A4 AWG2 AWG1 AWG2/0 AWG3/0 AWG
100 A4 AWG1 AWG2/0 AWG3/0 AWG4/0 AWG
150 A2 AWG2/0 AWG3/0 AWG4/0 AWG250 kcmil+
200 A1 AWG3/0 AWG4/0 AWG250 kcmil+Parallel / custom

Planning screen only (K≈12.9 Cu). 24 V / 48 V systems need less area for the same % drop—use the calculator presets and voltage-drop tool. Not a substitute for inverter manufacturer cable tables.

Ambient & grouping derating — screening reference

Illustrative correction factors only—do not stamp these numbers into a final design. Enter Ca/Cg from the adopted edition tables (for U.S. projects typically NEC 2023 ambient/adjustment notes under Art. 310; elsewhere IEC 60364-5-52, BS 7671 Appendix 4, etc.). This calculator’s mm² ladder is underrated from design current; Advanced Ca/Cg only inflate the screening current.

Example ambient correction (illustration only — not a code reprint)

Ambient (°C) Correction factor
21–251.00
31–350.94
41–450.88
51–550.82

Example bundling / grouping adjustment (NEC-style illustration)

Current-carrying conductors in raceway/cable Adjustment factor
1–31.00
4–60.80
7–90.70
10–200.50

Combined derating example: Design current 63 A → screening ladder suggests 16 mm² Cu. If ambient 41–45 °C (factor 0.88) and 4–6 grouped conductors (factor 0.80), required tabulated ampacity ≥ 63 ÷ (0.88 × 0.80) ≈ 89 A → upsize to the next ladder step (often 25 mm² for Cu screening). Then check voltage drop and OCPD coordination.

OCPD type (fuse vs breaker): see Fuse vs Breaker Sizing Guide.

Cable sizing method & formula context

I
Design load current in amperes (RMS, steady-state basis you are sizing for).
V
Nominal system voltage in volts (line-to-neutral for single-phase, line-to-line for three-phase).
mm²
Conductor cross-sectional area per IEC 60228 standard sizes; output here is always an integer mm² step.
Ampacity
Tabulated allowable current for a conductor under stated conditions; must be derated for grouping, ambient, and installation method.
PF (cos φ)
Power factor when converting from kW to kVA before finding line current.

Obtain design current: single-phase I = kVA × 1000 ÷ V; balanced three-phase I = kVA × 1000 ÷ (√3 × V) with √3 ≈ 1.732. From kW: kVA = kW ÷ PF, then use the line-current formula for your phase.

Screening rule (this tool): pick the smallest standard mm² whose ladder step current is ≥ I (or ≥ It when Advanced Ca/Cg are set, with It = Ib ÷ (Ca × Cg)). This is not a substitute for manufacturer ampacity tables, harmonics, insulation temperature rating (for example XLPE 90 °C), or short-circuit/adiabatic withstand proofs.

Solar / PV DC strings (solar panel cable size calculator path): Click the PV DC string · 27.5 A preset (Isc 11 A × 2 parallel × 1.25 → often ~6 mm² / ~10 AWG before derating), or enter your own Isc × N_parallel × continuous-current factor from the series-parallel calculator. Method: how to size solar DC cable. Confirm with MPPT sizing and the Solar calculators hub—this page absorbs solar DC cable screening; not a separate PV-cable-only tool.

Worked example: Module Isc 11 A, 2 parallel → 11 × 2 × 1.25 = 27.5 A design. Enter 27.5 A (DC 2-wire) on this calculator—screening often lands near ~6 mm² / ~10 AWG before derating and voltage-drop upsizing. Then check one-way length under Advanced / voltage drop.

DC wire size calculator / 12V wire size calculator path: Enter continuous DC amps (or use Quick presets), set Phase to DC (2-wire) and voltage to 12/24/48. Ampacity screen gives AWG + mm²; then set one-way length (ft) under Advanced and open NEC voltage drop—low-voltage DC % loss climbs fast on long runs. See also the battery cable size chart.

VFD / motor feeder screening: Use motor FLA × code factor (often 125%) as design amps, or the VFD preset (~63 A). This screens ampacity only—drive cable length, PWM reflections, and shield rules need manufacturer guidance after the ampacity + voltage-drop check.

Worked example (with numbers)

Given: 37 kW production load, PF 0.85, 400 V three-phase copper feeder.
Step 1 — kVA: 37 ÷ 0.85 ≈ 43.5 kVA.
Step 2 — line current: 43.5 × 1000 ÷ (1.732 × 400) ≈ 62.8 A → use 63 A design current.
Step 3 — screening mm²: 63 A maps to the next ladder step → 16 mm² Cu (integer output).
Step 4 — verify: apply grouping/ambient derating on project tables; check route length with the voltage drop calculator; confirm OCPD and fault current withstand with the breaker size calculator.

480 V three-phase · 100 A (SERP-style): Enter 100 A, 480 V, 3φ, Cu (or use the 480 V 3φ · 100 A preset). Screening often lands near 35 mm² / ~2 AWG before derating—then apply Ca/Cg and check NEC voltage drop for a 150 ft one-way run. This is a planning screen, not a full NEC Table 310.16 fill for every install method.

Common Cable Sizing Scenarios

Illustrative screening rows only—not a stamped bill of materials. AWG values below are read against NEC 2023 Table 310.16 copper columns under the stated temperature basis, ≤3 current-carrying conductors, and 30°C ambient before installation corrections. They do not auto-apply small-conductor OCPD limits (e.g. 240.4(D)-style), parallel-set rules, or terminal exceptions. Confirm on the locally adopted edition.

Scenario Load Screening AWG (Cu) mm² ladder Screening notes
Electric water heater4500W @ 240V = 18.75A12 AWG4 mm²If continuous, design often uses 125% → 23.4 A; verify OCPD/small-conductor rules
EV charger (Level 2)40A @ 240V8 AWG10 mm²Continuous EV loads often use 125% → 50 A; 75°C column screen ≈ 8 AWG when markings allow
10 HP motor @ 480V 3φFLC ≈ 14A (NEC Art. 430 tables)12 AWG4 mm²Prefer Motor Cable Size for 125% FLC + VD; VFD installs need separate checks
Main panel feed (100A)100A @ 240V3 AWG25 mm²75°C Cu screen ≈ 3 AWG / 100 A when terminations allow; 60°C basis may upsize —
Commercial lighting (20A circuit)20A @ 120/208V 3φ12 AWG4 mm²Common 20 A branch pairing; confirm adopted small-conductor/OCPD limits
Industrial feeder (200A)200A @ 480V 3φ3/0 AWG85 mm²75°C Cu screen ≈ 3/0; parallel sets for larger feeders are not modeled here

Voltage Drop Calculation Example

When cable runs are long, voltage drop often governs the size—not ampacity. Informational notes in many NEC editions mention about 3% on a branch and 5% feeder + branch total as planning targets—not automatic pass/fail ampacity rules. Use the resistive formula for a quick screen:

Vd = 2 × L × I × R ÷ 1000 (single-phase) or Vd = √3 × L × I × R ÷ 1000 (3-phase), where L = one-way length in feet, I = current in amps, R = conductor resistance in Ω/1000ft.

Example: 50A load, 240V single-phase, 100 ft one-way

Step 1: Ampacity-only screen → 8 AWG (50 A @ 75°C column when terminations allow) or larger on the 60°C column before installation-condition checks.

Step 2: Voltage drop check — 8 AWG R = 0.778 Ω/1000ft gives 7.78 V (3.24%), above the 3% target; upsize to 6 AWG, where 4.91 V = 2.05% of 240 V.

If run were 200 ft: Vd = 9.82V = 4.1% → exceeds 3%. Upsize to 4 AWG (R = 0.308 Ω/1000ft → Vd = 6.16V = 2.57%).

For 3-phase loads, replace the factor of 2 with √3 (1.732). For aluminum conductors, use ~1.6x the resistance of copper at the same AWG. Always confirm with manufacturer voltage drop tables for final design.

Installation method (why OEM tables still win)

Ampacity changes with how the cable is installed. Use Advanced Ca/Cg for a quick upsize; confirm final size on project IEC/NEC tables (Southwire/Eland-class tools encode these factors in brand software—we stay method-agnostic for planning).

Install methodPlanning note
In conduit / racewayHigher ambient + fill → apply Ca and count conductors for Cg
Cable trayGrouping and layering often force one mm² step up
Buried / duct bankSoil thermal resistivity dominates—use project tables, not this screen alone
Free airOften highest ampacity; still check VD on long outdoor runs

Use the suggested mm² as an early BOM or panel schedule checkpoint, then validate against detailed manufacturer tables including ambient, installation method, and voltage drop along the route.

Next step after screening: combine your candidate size with breaker frames and source ratings using the breaker size calculator, transformer size calculator, and generator size calculator, then confirm against IEC/NEC tables. Browse the protection calculators hub for the full lane.

Common standards designers cross-check

Cable sizing in practice is read against the locally adopted wiring rules and tabulated ampacity—for U.S. projects this page’s AWG screen is bound to NEC 2023 Table 310.16 (older editions used 310.15(B)(16)); elsewhere use IEC 60364, BS 7671, AS/NZS 3008, or manufacturer tables. The mm² output is an IEC 60228-style ladder for early screening, not a full IEC ampacity selection for installation method.

NEC / AWG cross-check for US projects

After you have a candidate mm², map to approximate AWG/kcmil and confirm allowable amps under the adopted NEC edition (temperature rating, ambient, bundling, small-conductor/OCPD limits, and whether parallel conductors apply). The AWG screen on this page uses NEC 2023 Table 310.16 columns selected in Advanced; it still does not size parallel sets.

Screening mm² (Cu) Approx. AWG Illustrative NEC 2023 Cu screen (60°C / 75°C) Load
1.516 AWG~15 A / ~20 A
2.514 AWG~20 A / ~25 A
412 AWG~25 A / ~30 A
610 AWG~30 A / ~35 A
108 AWG~40 A / ~50 A
166 AWG~55 A / ~65 A
254 AWG~70 A / ~85 A
352 AWG~95 A / ~115 A · 100 A screen
501 AWG~110 A / ~130 A
702/0 AWG~145 A / ~175 A
953/0 AWG~165 A / ~200 A

Quick PAA — what size wire for 100 amp service? At 240 V 1φ, many NEC 75°C Cu screens land near 3 AWG (use the 100 A panel · 240 V preset). At 480 V 3φ, screening often lands near 3 AWG Cu / 1 AWG Al (75°C) or ~35 mm² on the IEC ladder—always apply ambient/bundling and match OCPD with the breaker size calculator.

3-phase motor cable sizing (FLA screen)

Motors: take nameplate or NEC Table 430.250 FLA, apply continuous/branch factors from your code (often 125% of FLA for conductors), enter that design amps above for mm² screening, then map to AWG. Example: ~50 HP @ 460 V ≈ 65 A FLA → 65 × 1.25 ≈ 81 A → screening ladder often ~25 mm² / 4 AWG Cu before voltage drop and starting voltage dip—see motor starting & protection.

Last updated: 2026-09-15. mm² screening + AWG illustration only—not a reprint of NEC Table 310.16 or IEC 60364-5-52.

References

Installation method, grouping & fault current

Real ampacity depends on how the run is installed—for example in conduit, on cable tray, buried, or in free air—together with grouping/bundling and ambient temperature derating. Use Advanced Ca/Cg for a quick upsized screen; still confirm final ampacity on your IEC/NEC project tables.

Fault current & protection: available fault current, device let-through, and adiabatic thermal limits can require a larger conductor than steady-state ampacity. Size OCPD and check short-circuit withstand after screening—see the breaker size calculator and motor starting & protection guide for coordination context.

More context: Voltage drop calculation · kW to kVA Formula Explained · 3-Phase Power Calculator · When to Use kVA Instead of kW

3-phase cable size chart (kW → A → mm² / AWG)

Screening table for kW to cable size at 400 V / 480 V three-phase (PF 0.85). Also covers searches for a 3 phase cable size calculator chart—use Quick presets for 10 kW / 15 kW, then verify voltage drop.

Screening look-up at PF 0.85 copper, underrated (Ca = Cg = 1). Line current Ib = P ÷ (√3 × V × PF). AWG is an approximate NEC cross-check only. Enter the same kW in the calculator (From kW) or apply Advanced derating when ambient/grouping apply.

Load (kW) Ib @ 400 V (A) mm² / AWG @ 400 V Ib @ 480 V (A) mm² / AWG @ 480 V
1017.02.5–4 / 14–12 AWG14.12.5 / 14 AWG
1525.54 / 12 AWG21.24 / 12 AWG
2237.46 / 10 AWG31.16 / 10 AWG
3051.010 / 8 AWG42.510 / 8 AWG
3762.816 / 6 AWG52.410 / 8 AWG
4576.525 / 4 AWG63.716 / 6 AWG
5593.525 / 4 AWG77.825 / 4 AWG
75127.435 / 2 AWG106.235 / 2 AWG
100169.950 / 1 AWG141.650 / 1 AWG

After screening, check long feeders on the voltage drop calculator and OCPD on the breaker size calculator.

Frequently Asked Questions

How do I size solar / PV DC cable?

Compute array current from module Isc × parallel strings (see series-parallel), apply your code’s continuous-current factor (often 1.25× on Isc), enter that design amps here for mm² screening, then check DC voltage drop on long runs. Example: Isc 11 A × 2P × 1.25 = 27.5 A → use the PV DC string Quick preset or jump to #solar-dc-cable—often screens near ~6 mm² / ~10 AWG before derating. Hub: Solar calculators hub—no separate solar-DC-only cable page.

How do I size 12 V battery or inverter DC cable?

Enter continuous DC amps (or click the 12 V battery / 48 V inverter preset), set Phase to DC (2-wire) and voltage to 12/24/48. Read the NEC-style AWG screen and IEC mm², enter one-way length in feet under Advanced, or start from the battery cable size chart, then check 12 V / DC voltage drop—percent loss is much higher than on 120 V AC for the same gauge.

Is this a wire gauge length calculator?

Ampacity (AWG/mm²) comes from design current. Enter one-way length under Advanced and choose a 3% or 5% VD planning limit to upsize AWG/mm² when the resistive screen exceeds the target (ampacity + drop on one page). Still open NEC voltage drop for the full K-method check—or use the % drop table for a quick 20 A look-up.

Is this a wire size calculator / wire gauge size calculator?

Yes. This online wire size calculator screens AWG and mm² from design amps or kW for single-phase AC, three-phase AC, and DC. Use the AWG/NEC cross-check or the AWG cable size chart for wire gauge size / gauge cable size. Optional Advanced length + 3%/5% couples voltage-drop upsizing. Also covers 3-phase cable size, 12V wire size / battery cable size, and VFD feeders.

How do I choose wire size for a 120V circuit?

Select single-phase AC and 120 V, enter design current (or click 120 V branch · 20 A · 100 ft), then read AWG/mm² from the wire and cable size chart. Add one-way length under Advanced if drop may govern. Confirm insulation, terminals, and OCPD on your adopted code—planning screen only.

Can I use this as a DC wire size calculator or 12V wire size calculator?

Yes. Set Phase to DC (2-wire) and voltage to 12/24/48, enter continuous DC amps (or use the 12 V battery / 48 V inverter preset), then read AWG and mm². Low-voltage DC is often voltage-drop limited—see DC / 12V notes, the battery cable size chart, and NEC DC voltage drop.

Does voltage drop change the wire size I need?

Often yes on long runs. Enter one-way length and a 3% or 5% planning limit under Advanced so this page can upsize the AWG/mm² screen when resistive drop exceeds the target—then open the voltage drop calculator for the full check. 3%/5% are planning notes, not automatic pass/fail code limits.

What is a cable size calculator?

A cable size calculator screens IEC-style mm² from design amps and conductor material (Cu/Al). Example: 32 A copper → 6 mm² on the screening ladder—then apply derating and check voltage drop on long runs.

How do I calculate 3 phase cable size?

To calculate 3 phase cable size, enter From kW with PF and voltage (Ib = P ÷ (√3 × V × cos φ)), or enter design amps directly. Then screen the next standard mm² from this calculator’s IEC-style ladder, optionally apply Advanced Ca/Cg derating, and verify voltage drop on the actual run length.

What size cable for 10 kW three-phase?

At 400 V three-phase and PF 0.85, 10 kW → Ib ≈ 17.0 A; screening often lands near 2.5–4 mm² / ~14–12 AWG copper before derating and voltage drop. Click the 10 kW · 400 V 3φ Quick preset, then confirm ambient/bundling and long-run drop on the voltage drop calculator.

What size cable for 15 kW three-phase?

At 400 V three-phase and PF 0.85, 15 kW → Ib ≈ 25.5 A; the kW→cable chart screens about 4 mm² / 12 AWG copper before derating. Use the 15 kW preset, then verify voltage drop and OCPD.

How to calculate cable size in sq mm?

Compute design current Ib (from amps, or from kW: three-phase Ib = P ÷ (√3 × V × PF)), pick the next standard mm² on the IEC-style ladder that meets Ib after Ca/Cg derating, then check voltage drop on the run length. This calculator returns the mm² screen plus an NEC-style AWG cross-check.

How do bundled cables affect ampacity?

Grouped conductors reduce heat dissipation, so tabulated ampacity must be multiplied by a grouping derating factor from IEC 60364 or NEC tables. Use Advanced → Grouping correction Cg for a quick upsized screen (It = Ib ÷ (Ca × Cg)), then confirm on your project tables.

What is the ampacity of a wire?

Wire ampacity is the maximum continuous current a conductor can carry without exceeding its insulation temperature rating. The wire ampacity chart above lists allowable ampacities by AWG size, conductor material (copper vs aluminum), and insulation temperature column (60/75/90 °C, NEC Table 310.16-style) — then the calculator converts your design current into a size after derating and voltage drop.

What is the NEC code for wire ampacity?

NEC Table 310.16 (2023 edition; in earlier editions numbered 310.15(B)(16)) lists allowable ampacities of insulated conductors rated 0–2000 V, with up to three current-carrying conductors in raceway or cable at 30 °C ambient. Higher ambient or bundled conductors require correction/adjustment factors from the adjacent NEC articles — always confirm against your adopted edition.

Will #10 wire carry 40 amps?

Not on the usual termination columns: NEC Table 310.16 lists 10 AWG copper at 30 A (60 °C) / 35 A (75 °C) / 40 A (90 °C column), and NEC 240.4(D) caps small-conductor overcurrent protection at 30 A for 10 AWG. A 40 A circuit typically uses 8 AWG copper (or larger aluminum) — enter 40 A above for a derated, voltage-drop-checked size.

Is 4 AWG rated for 100 amps?

4 AWG copper is 70/85/95 A at the 60/75/90 °C columns of NEC Table 310.16, so it is not rated for 100 A. A 100 A circuit at 75 °C typically needs 3 AWG copper or 1/0 aluminum; enter 100 A design current in the calculator above for the derated screen.

What ambient temperature derating should I apply?

Use the correction factor from your wiring code for the conductor insulation rating (for example 70 °C or 90 °C PVC/XLPE) and the expected ambient—or pick an illustrative Ca under Advanced. High ambient or enclosed trays often push you one mm² step—or more—above a current-only screening value.

When does fault current require a larger conductor?

Short-circuit thermal limits (adiabatic withstand) can force a larger cross-section than steady-state ampacity. Check available fault current, protection device let-through, and manufacturer k²S² limits—use the breaker size calculator and project fault studies after screening mm² here.

Can you provide a cable sizing example with numbers?

Given: 37 kW, PF 0.85, 400 V three-phase → kVA ≈ 43.5, line current I ≈ 63 A. Screening ladder → 16 mm² Cu. Then verify grouping derating and route voltage drop before locking the BOM.

How does mm² relate to AWG for NEC projects?

IEC 60228 uses metric mm²; NEC projects often specify AWG/kcmil. Approximate cross-checks: 6 mm² ≈ 10 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG, 70 mm² ≈ 2/0 AWG—see the NEC / AWG cross-check table. Always confirm against NEC Table 310.16 (or your adopted edition) for insulation and installation method.

What size cable for 100 A at 480 V three-phase?

As a screening illustration, ~100 A continuous at 480 V 3-phase often lands near 3 AWG Cu (75 °C) or 1 AWG Al on many NEC ampacity readings—or ~35 mm² on this page’s IEC-style ladder before derating. Apply ambient/bundling corrections and match OCPD; use the calculator with 100 A design current.

How do I size cable for a 3-phase motor?

Use motor FLA (nameplate or NEC 430.250), apply your code’s conductor factor (often 125% of FLA), enter that amps above for mm², then map to AWG. Example: ~50 HP @ 460 V ≈ 65 A FLA → ~81 A → often ~25 mm² / 4 AWG Cu before voltage-drop checks. See motor cable sizing.

How do harmonics affect cable sizing?

Non-linear loads add harmonic current that increases conductor heating and neutral loading. Derating or upsizing may be required beyond a fundamental-frequency ampacity check—this page assumes steady-state RMS design current only.

What is the difference between copper and aluminum cables?

Copper has higher conductivity, so it carries more current for the same cross-section and is more compact, but more expensive. Aluminum is lighter and cheaper but often requires a larger cross-section and special terminations.

How does voltage drop affect cable sizing?

Long runs at high current can cause significant voltage drop. In many standards you must keep voltage drop below a specified percentage, which may require a larger cable than indicated by current capacity alone—use the voltage drop calculator after screening.

What standards do engineers cross-check for cable sizing?

Designers cross-check IEC 60364, NEC ampacity chapters, BS 7671, or AS/NZS 3008 plus manufacturer data for insulation temperature rating. This tool does not replace those tables or statutory compliance.

Where is the cable size chart?

Use the AWG cable size chart (gauge → mm² / circular mils / copper ampacity), the cable size chart (amps → AWG / mm²), the battery cable size chart for 12 V DC length screens, or the 3-phase kW chart. Voltage drop often forces upsizing on long runs.

Is gauge cable size the same as AWG?

Yes. In North American power wiring, gauge cable size usually means American Wire Gauge (AWG). Use the AWG cable size chart for mm², circular mils, and copper ampacity—then size from load amps with the calculator if you do not already know the gauge.

What AWG is 2.5 mm wire?

2.5 mm² is closest to 14 AWG by area (14 AWG ≈ 2.08 mm²). Matches are approximate—confirm ampacity and terminals on project tables. See the metric column on the AWG cable size chart.

What is the area of a 10 AWG wire in circular mils?

10 AWG is about 10,380 circular mils (≈ 5.26 mm²). Read the circular mils column on the AWG cable size chart.

What is the cross-sectional area of 12 AWG wire?

12 AWG is about 3.31 mm² (≈ 6,530 circular mils). Use the AWG cable size chart for copper ampacity next to area.

How can I tell what size copper wire I have?

Read the printed AWG marking on the insulation when present. If unmarked, measure conductor diameter or area and match the copper cable size chart / AWG table—do not rely on overall jacket OD alone for stranded cable.

Ampacity chart vs voltage-drop path—what do I do after the chart?

The ampacity chart screens AWG/mm² from design current. After that chart step, verify long runs on the voltage drop calculator—drop limits often force a larger conductor than ampacity alone. For OCPD and protection workflow, continue on the Protection calculator hub.

Do you have a conduit sizing for wire calculator?

No dedicated conduit-fill tool. Size the conductor here first, then select raceway trade size from NEC Chapter 9 Annex C (or manufacturer fill). See conduit note—ampacity in conduit still needs Ca/Cg derating.

Does the calculator change results by installation method (conduit, tray, buried)?

Optionally. Use Advanced Ca (ambient) and Cg (grouping) to inflate the screening current. Real ampacity still depends on installation method (conduit, cable tray, buried, or free air); confirm correction factors on your project tables after you have a candidate mm².

Is this calculator suitable for final design?

No. It is intended for quick checks and concept design. Final cable selection must follow detailed tables from standards and manufacturers, and should be validated by a qualified electrical engineer.