Generator load
- Load
- 100 kW
- PF
- 0.80
- Required kVA
- 125 kVA
- Recommended
- 150 kVA
Reserve 20% for startup current and future expansion.
Free kW to kVA converter: enter kW and power factor in the calculator below for generators, UPS, transformers, and single- or three-phase loads.
Power factor links real kW to apparent kVA. Read the cluster authority guide for formulas, typical industrial values, and correction methods before you size equipment.
Quick: value and PF presets. Advanced: conversion direction and PF band refine kVA for mixed motor / IT loads.
Used by engineers for electrical load calculation and equipment sizing. A kW to kVA conversion chart at 0.85 PF is below the calculator; expand View full reference table to filter all checkpoints and open prefilled links here.
Tip: Adjust kW or PF to instantly update the result.
Turn planning kW and a realistic power factor into required kVA for motors, UPS systems, distribution transformers, and general industrial loads, before you size feeders or upstream equipment. For broader energy and current workflows, use the power calculator hub. Switch Conversion Direction to kVA → kW when you need the reverse (e.g. 1 kVA @ 0.8 PF → 0.8 kW).
Based on standard power factor assumptions used in industrial equipment sizing.
This calculator provides power conversion estimates only. For final electrical system design, equipment sizing, and power factor correction, consult a licensed electrical engineer or certified professional. Actual power requirements may vary based on detailed load analysis, harmonics, and specific application requirements.
Use kVA = kW ÷ PF at 0.85 PF. The chart lists common kW steps for generator and transformer planning. Open a row to load values in the calculator, or expand View full reference table for all 35 kW steps with a filter.
| Real Power (kW) | Power Factor (PF) | Apparent Power (kVA) | Calculator |
|---|---|---|---|
| 1 | 0.85 | 1.18 | Open |
| 5 | 0.85 | 5.88 | Open |
| 10 | 0.85 | 11.76 | Open |
| 20 | 0.85 | 23.53 | Open |
| 25 | 0.85 | 29.41 | Open |
| 30 | 0.85 | 35.29 | Open |
| 50 | 0.85 | 58.82 | Open |
| 63 | 0.85 | 74.12 | Open |
| 75 | 0.85 | 88.24 | Open |
| 100 | 0.85 | 117.65 | Open |
| 125 | 0.85 | 147.06 | Open |
| 200 | 0.85 | 235.29 | Open |
| 250 | 0.85 | 294.12 | Open |
| 500 | 0.85 | 588.24 | Open |
| 1000 | 0.85 | 1176.47 | Open |
| Real Power (kW) | Power Factor (PF) | Apparent Power (kVA) | Calculator |
|---|---|---|---|
| 1 | 0.85 | 1.18 | Open |
| 2 | 0.85 | 2.35 | Open |
| 3 | 0.85 | 3.53 | Open |
| 4 | 0.85 | 4.71 | Open |
| 5 | 0.85 | 5.88 | Open |
| 6 | 0.85 | 7.06 | Open |
| 7 | 0.85 | 8.24 | Open |
| 8 | 0.85 | 9.41 | Open |
| 9 | 0.85 | 10.59 | Open |
| 10 | 0.85 | 11.76 | Open |
| 12 | 0.85 | 14.12 | Open |
| 15 | 0.85 | 17.65 | Open |
| 18 | 0.85 | 21.18 | Open |
| 20 | 0.85 | 23.53 | Open |
| 22 | 0.85 | 25.88 | Open |
| 25 | 0.85 | 29.41 | Open |
| 30 | 0.85 | 35.29 | Open |
| 35 | 0.85 | 41.18 | Open |
| 40 | 0.85 | 47.06 | Open |
| 45 | 0.85 | 52.94 | Open |
| 50 | 0.85 | 58.82 | Open |
| 63 | 0.85 | 74.12 | Open |
| 75 | 0.85 | 88.24 | Open |
| 90 | 0.85 | 105.88 | Open |
| 110 | 0.85 | 129.41 | Open |
| 125 | 0.85 | 147.06 | Open |
| 160 | 0.85 | 188.24 | Open |
| 200 | 0.85 | 235.29 | Open |
| 250 | 0.85 | 294.12 | Open |
| 315 | 0.85 | 370.59 | Open |
| 400 | 0.85 | 470.59 | Open |
| 500 | 0.85 | 588.24 | Open |
| 630 | 0.85 | 741.18 | Open |
| 800 | 0.85 | 941.18 | Open |
| 1000 | 0.85 | 1176.47 | Open |
Same page, opposite direction: kW = kVA × PF. Common steps at 0.8 PF (typical motors/generators) and 0.85 PF (industrial planning). Primary workflow remains kW → kVA above.
To convert kW to kVA (kilowatts to kilovolt-amperes), divide real power by power factor: kVA = kW ÷ PF. This applies to single-phase and balanced three-phase when you use total kW and an equivalent PF.
kVA = kW / Power Factor (PF)
If you have 10 kW at 0.85 power factor, apparent power is: kVA = 10 ÷ 0.85 = 11.76 kVA
Tip: Use the kW to kVA calculator above for instant results at 0.8, 0.85, 0.9, or any custom PF between 0.1 and 1.0 — including kW ↔ kVA reverse mode.
kW vs kVA: kW is real power (does work); kVA is apparent power (must be supplied by the source or equipment rating).
Mechanical loads are often rated in hp (horsepower). Use 1 hp ≈ 0.746 kW (IEC) to express motor power in kW, then use the calculator with your PF.
Quick answer: Use kW = kVA × PF. For 1 kVA: PF 1.0 → 1.0 kW · PF 0.85 → 0.85 kW · PF 0.8 → 0.8 kW. There is no single fixed convert without PF. Open 1 kVA → kW @ 0.8 PF (same calculator; primary mode remains kW → kVA).
Example: 1 kVA at 0.8 PF → kW = 1 × 0.8 = 0.8 kW. Enter PF from nameplate or field data; motors often sit near 0.80–0.90 and many IT loads near 0.95. For three-phase line voltage and current relationships, see 3-Phase Power Calculator.
Need kVA → kW? Open kVA → kW mode (this tool) or choose kVA → kW under Conversion Direction in the calculator above. After you have kVA, continue sizing with kVA to amps or transformer sizing when needed.
More context: 3-phase power formula · Power factor formula · kW vs kVA · 3-phase power calculator · kVA to amps · Transformer sizing · Power Calculators Hub
kVA² = kW² + kVAR²; with PF known, PF = kW ÷ kVA.
After kVA = kW ÷ PF, add application-specific planning margins before you order equipment. Values below are computed from the same sizing rules as the live calculator preview.
Reserve 20% for startup current and future expansion.
Next standard UPS frame with 15% planning headroom (IT-style PF when applicable).
Next standard transformer kVA with 10% margin for continuous industrial load.
Typical power factor and planning recommendation by application—computed with configured margins, not a raw conversion chart. Use the calculator for your load.
| Application | Typical PF | Required kVA | Recommendation |
|---|---|---|---|
| Generator backup | 0.80 | 125 | 150 kVA |
| UPS / IT bus | 0.95 | 105 | 160 kVA |
| Induction motor | 0.85 | 118 | 160 kVA |
| Transformer load | 0.90 | 222 | 250 kVA |
| VFD drive | 0.96 | 78.1 | 100 kVA |
| HVAC chiller | 0.88 | 284 | 350 kVA |
| Data center row | 0.95 | 84.2 | 100 kVA |
| General mixed load | 0.85 | 74.1 | 100 kVA |
Treating kW as kVA is the most frequent sizing error—motors and mixed plants rarely run at unity PF.
Recommendation: Always divide kW by a realistic PF before you match generator, UPS, or transformer catalog frames.
Steady-state kVA does not cover motor starting, harmonics, or planned expansion.
Recommendation: Add 10–25% planning margin in the dedicated sizing tool after this converter gives baseline kVA.
Nameplate PF, measured PF, and application defaults differ—IT loads often exceed 0.95 while induction motors sit near 0.80–0.90.
Recommendation: Use measured data when available; otherwise pick an application-specific PF in the decision table below.
Oversized sources improve headroom but increase cost, losses, and minimum loading issues.
Recommendation: Round up to the next standard frame only after margin rules—not every intermediate kVA step is a catalog size.
Undersizing apparent power risks overload alarms, breaker nuisance trips, and voltage depression during inrush.
Recommendation: If required kVA is within ~10% of the next catalog step, treat the frame as tight and verify in the downstream tool.
Motor and transformer energization can draw several times steady kVA for seconds.
Recommendation: Use generator and UPS sizing tools for inrush factors—this page models steady kW ÷ PF only.
Move from apparent power to current, protection, conductors, and backup planning.
Understand power factor formulas, utility penalties, and correction workflows in the Power Systems cluster authority guide.
Divide real power by power factor: kVA = kW ÷ PF. Example: 10 kW at PF 0.85 = 11.76 kVA. Enter kW and PF in the calculator for any load.
Multiply by power factor: kW = kVA × PF. At PF 1.0, 1 kVA = 1 kW. At 0.85 PF, 1 kVA ≈ 0.85 kW. At 0.8 PF, 1 kVA = 0.8 kW. Open 1 kVA → kW @ 0.8 PF in the calculator.
It depends on PF. At 0.85 PF, 1 kW ≈ 1.18 kVA. At 0.80 PF, 1 kW = 1.25 kVA. Open 1 kW @ 0.85 PF in the calculator.
Only when power factor is 1.0 (unity). At typical industrial 0.85 PF, 1 kW ≈ 1.18 kVA because apparent power must cover real power plus reactive load. Compare 1 kW at your PF.
kWh is energy (kilowatts × hours); kVA is instantaneous apparent power—you cannot swap them without a time interval. 1 kWh means 1 kW of real energy consumed over one hour. At PF 0.85, that hour averaged about 1.18 kVA of apparent power (1 ÷ 0.85). For equipment sizing at a steady load, convert kW → kVA with kVA = kW ÷ PF in the calculator.
No. One mechanical horsepower (HP) ≈ 0.746 kW (745.7 W). So 1 kW ≈ 1.34 HP, and a 1 HP motor draws about 0.75 kW at full load before efficiency and PF. Convert HP to kW, then use kVA = kW ÷ PF for transformer or generator sizing. See the HP note in Conversion Chart.
At PF 0.85, 10 kW = 11.76 kVA (10 ÷ 0.85). Open 10 kW in the calculator or adjust PF for your equipment.
Not usually—60 kVA = 60 kW only at PF 1.0. At 0.85 PF, 60 kW ≈ 70.6 kVA (60 ÷ 0.85). Try 60 kW @ 0.85 PF in the calculator.
In kW/kVA searches, KV often means kVA (typo), not kilovolts. If you mean 1 kVA at 0.85 PF, real power ≈ 0.85 kW (kW = kVA × PF). For voltage in kV, that is a different unit—use your line voltage in the kVA to amps tool.
At PF 0.85, 20 kVA ≈ 17 kW real power (kW = kVA × PF). At unity PF, 20 kVA = 20 kW. Adjust PF in the calculator for your load.
At PF 0.85, 20 kVA ≈ 17 kW (kW = kVA × PF). At PF 1.0, 20 kVA = 20 kW. Enter 20 kVA equivalent load and your PF in the calculator.
At PF 0.85, 20 kW ≈ 23.53 kVA (20 ÷ 0.85). Open 20 kW @ 0.85 PF in the calculator.
At PF 0.85, 7 kW ≈ 8.24 kVA (7 ÷ 0.85). Calculate 7 kW with your PF.
At PF 0.85, 25 kW ≈ 29.41 kVA (25 ÷ 0.85). Prefill 25 kW in the calculator.
At PF 0.85, 50 kW ≈ 58.82 kVA (50 ÷ 0.85). See the conversion chart or open 50 kW in the calculator.
At PF 0.85, 100 kW ≈ 117.65 kVA (100 ÷ 0.85). Calculate 100 kW with your PF.
At PF 0.85, 200 kW ≈ 235.29 kVA (200 ÷ 0.85). Add design headroom before generator or transformer selection.
Use nameplate or measured PF first. If unavailable, start with 0.80–0.90 for motors or 0.95 for IT loads, then verify with the calculator. For UPS sizing, continue to the UPS capacity calculator after kVA—see also UPS efficiency and losses when PF or η limits runtime.
At the same kW, lower PF means more apparent power is needed. Use the calculator to compare different PF values and see required kVA instantly.
Yes—enter any kW and PF to get kVA instantly. Formula: kVA = kW ÷ PF. Example: 100 kW @ 0.8 PF = 125 kVA. Open the converter.
Use the same formula on this page: kVA = kW ÷ PF with total three-phase kW and an equivalent PF. Then continue to kVA to amps (3-phase) for line current. For V–I–PF relationships, see 3-Phase Power Calculator.
Start from nameplate or measured kW, apply a realistic PF to estimate kVA, then add 15–25% design headroom for harmonics, inrush, and load variation before selecting equipment. Validate assumptions with a licensed engineer for final design.
Reviewed: CalcPanel Electrical Engineering Team
Updated: 2026-06-29
Featured: kW to kVA Calculator